25 resultados para Superconducting fault current limiter


Relevância:

100.00% 100.00%

Publicador:

Resumo:

A single-phase superconducting fault current limiter (SFCL) using a 0.9 m length of YBCO coated conductor (CC) tape was tested in 220 V-60 Hz line for fault current up to 1 kA, operating in 77 K. In this work are presented the IN experimental curves measured under DC and AC currents for the electrical characterization of the CC tape in order to design a low voltage current limiter. The experimental setup is described and the test results are presented for a unit conducting a steady nominal AC current of 50 A and also during the fault time (I to 5 cycles.) the performance of the CC-based SFCL providing the limiting resistance developed in the whole tape length after few milliseconds of the beginning of the fault was analyzed.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Resistive-type of superconducting fault current limiters (RSFCL) have been developed for medium voltage class aiming to operate at 1 MVA power capacity and short time recovery (< 2 s). A RSFCL in form of superconducting modular device was designed and constructed using 50 m-length of YBCO coated conductor tapes for operation under 1 kV / 1 kA and acting time of 0.1 s. In order to increase the acting time the RSFCL was combined with an air-core reactor in parallel to increase the fault limiting time up to 1 s. The tests determined the electrical and thermal characteristics of the combined resistive/ inductive protection unit. The combined fault current limiter reached a limiting current of 583 A, corresponding to a limiting factor of 3.3 times within an acting time of up to 1 s.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

100.00% 100.00%

Publicador:

Resumo:

In this work, we report on the evaluation of a superconducting fault current limiter (SFCL). It is consisted of a modular superconducting device combined with a short-circuited transformer with a primary copper winding connected in series to the power line and the secondary side short-circuited by the superconducting device. The basic idea is adding a magnetic component to contribute to the current limitation by the impedance reflected to the line after transition of the superconducting device. The evaluation tests were performed with a prospective current up to 2 kA, with the short-circuited transformer of 2.5 kVA, 220 V/660 V connected to a test facility of 100 kVA power capacity. The resistive SFCL using a modular superconducting device was tested without degradation for a prospective fault current of 1.8 kA, achieving the limiting factor 2.78; the voltage achieved 282 V corresponding to an electric field of 11 V/m. The test performed with the combined SFCL (xsuperconducting device + transformer) using series and toroidal transformers showed current limiting factor of 3.1 and 2 times, respectively. The test results of the combined SFCL with short-circuited transformer showed undesirable influence of the transformer impedance, resulting in reduction of the fault current level. © 2002-2011 IEEE.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

A superconducting fault current limiter (SCFL) consisted of a transformer with low reactance connected to the power line and with the secondary winding short-circuited by a modular superconducting limiter device with 16 elements connected in series was constructed and tested. The designed coupling transformer has low dispersion reactance in order to limit the voltage drop in the power line within the range of 5 % to 10 %. The experimental results showed that an insertion of a 0.125 Omega resistance limited the peak current to a factor of 2.5 times of the unlimited current. The power dissipation reached 39 kW during 100 ms, with an energy density of 380 J/cm(3). Based on these results, the SCFL will be further tested in a 3 MVA (15 kV/380 V) generator for currents up to 10 kA.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

A Fault Current Limiter (FCL) based on high temperature superconducting elements with four tapes in parallel were designed and tested in 220 V line for a fault current peak between 1 kA to 4 kA. The elements employed second generation (2G) HTS tapes of YBCO coated conductor with stainless steel reinforcement. The tapes were electrically connected in parallel with effective length of 0.4 m per element (16 elements connected in series) constituting a single-phase unit. The FCL performance was evaluated through over-current tests and its recovery characteristics under load current were analyzed using optimized value of the shunt protection. The projected limiting ratio achieved a factor higher than 4 during fault of 5 cycles without degradation. Construction details and further test results will be shown in the paper. © 2010 IOP Publishing Ltd.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

A bifilar Bi-2212 bulk coil with parallel shunt resistor was tested under fault current condition using a 3 MVA single-phase transformer in a 220 V-60 Hz line achieving fault current peak of 8 kA. The fault current tests are performed from steady state peak current of 200 A by applying controlled short circuits up to 8 kA varying the time period from one to six cycles. The test results show the function of the shunt resistor providing homogeneous quench behavior of the HTS coil besides its intrinsic stabilizing role. The limiting current ratio achieves a factor 4.2 during 5 cycles without any degradation.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

The resistive-type superconducting fault current limiters (RSFCL) prototypes using YBCO-coated conductors have shown current limitation for medium voltage class applications for acting time up to 80 ms. By connecting an air-core reactor in parallel with the RSFCL, thus making an hybrid current limiter, one can extend the acting time for up to 1 s. In this work, we report the performance of a hybrid current limiter subjected to an AC peak fault current of 2 kA during 1 s for which within the first 80 ms the SFCL limits the current concurrently with the air-core reactor, and for the remaining 920 ms, only the air-core reactor limits the current. In order to evaluate the actual conditions for subsequent reconnection of RSFCL to the power grid, the hybrid fault current limiter was tested varying the time interval for recovery from 900 ms and 1.2 s, followed again by the concurrent operation of the hybrid limiter during 1 s (SFCL during 80 ms). From this evaluation test, the recovery time can be measured and compared using the voltage peak generated in superconducting module from the first and second fault test. The recovery time was also determined through the pulsed current method (PCM) on short-length sample test. The results showed that the fault current was limited from 1.9 kA down to 514 A after 1 cycle of 60 Hz frequency, with recovery time lower than 1.2 s for two subsequent fault current tests.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

A single-phase superconducting Fault Current Limiter using a bifilar coil of BSCCO-2212 tube was tested in 220 V-60 Hz line during fault current between 1 kA to 4 kA, operating in 77 K. In this work are presented the critical current dependence as a function of an external magnetic field applied and the results can be used to predict the current limiter performance. The experimental setup is described and the test results are presented for the unit conducting a steady nominal AC current of 200 A, and also during the fault time (1 to 6 cycles). The performance of the bifilar coil to provide the limiting impedance associated with the dynamic resistance developed during the beginning of the fault was analyzed and compared with other types of superconducting current limiters.

Relevância:

40.00% 40.00%

Publicador:

Resumo:

In this contribution superconducting specimens of YBa(2)Cu(3)O(7-delta) were synthesized by a modified polymeric precursor method, yielding a ceramic powder with particles of mesoscopic-size. Samples of this powder were then pressed into pellets and sintered under different conditions. The critical current density was analyzed by isothermal AC-susceptibility measurements as a function of the excitation field, as well as with isothermal DC-magnetization runs at different values of the applied field. Relevant features of the magnetic response could be associated to the microstructure of the specimens and, in particular, to the superconducting intra- and intergranular critical current properties.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

30.00% 30.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

30.00% 30.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)