Test results of fault current limiter using YBCO tapes with shunt protection
Contribuinte(s) |
Universidade Estadual Paulista (UNESP) |
---|---|
Data(s) |
27/05/2014
27/05/2014
01/12/2010
|
Resumo |
A Fault Current Limiter (FCL) based on high temperature superconducting elements with four tapes in parallel were designed and tested in 220 V line for a fault current peak between 1 kA to 4 kA. The elements employed second generation (2G) HTS tapes of YBCO coated conductor with stainless steel reinforcement. The tapes were electrically connected in parallel with effective length of 0.4 m per element (16 elements connected in series) constituting a single-phase unit. The FCL performance was evaluated through over-current tests and its recovery characteristics under load current were analyzed using optimized value of the shunt protection. The projected limiting ratio achieved a factor higher than 4 during fault of 5 cycles without degradation. Construction details and further test results will be shown in the paper. © 2010 IOP Publishing Ltd. |
Identificador |
http://dx.doi.org/10.1088/1742-6596/234/3/032002 Journal of Physics: Conference Series, v. 234, n. PART 3, 2010. 1742-6588 1742-6596 http://hdl.handle.net/11449/72008 10.1088/1742-6596/234/3/032002 2-s2.0-78650867520 |
Idioma(s) |
eng |
Relação |
Journal of Physics: Conference Series |
Direitos |
closedAccess |
Palavras-Chave | #Effective length #Fault currents #Fault-current limiter #High temperature superconducting #HTS tapes #Load currents #Over current #Second generation (2G) #Stainless steel reinforcement #Test results #YBCO coated conductors #YBCO tape #Critical current density (superconductivity) #Electric fault currents #High temperature superconductors #Limiters #Stainless steel #Superconductivity #Yttrium barium copper oxides #Superconducting tapes |
Tipo |
info:eu-repo/semantics/conferencePaper |