236 resultados para high voltage


Relevância:

60.00% 60.00%

Publicador:

Resumo:

In the case of an ac cable, power transmission is limited by the length of the cable due to the capacitive reactive current component. It is well known that high-voltage direct current (HVDC) cables do not have such limitations. However, insulation-related thermal problems pose a limitation on the power capability of HVDC cables. The author presents a viable theoretical development, a logical extension to Whitehead's theory on thermal limitations of the insulation. The computation of the maximum power-carrying capability of HVDC cables subject to limits on the maximum operable temperature of the insulation is presented. The limitation on the power-carrying capability is closely associated with the electrothermal insulation failure. The effect of environmental interaction by way of external thermal resistance, an important aspect, is also considered in the formulations. The Lagrange multiplier method has been used to handle the ensuing optimization problem. The theory is based on an accepted theory of thermal breakdown in insulation and is an important and a coherent extension of great significance.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

A simple equation to predict the breakdown voltages for binary mixtures (Vmix) of electronegative gases (SF6, CCl2F2) and buffer gases (N2, N2O, CO2, air) under uniform electric field has been proposed. Values of Vmix evaluated using this equation for mixtures of SF6-N2, SF6-air, SF6-N2O, SF6-CO2 and CCl2F2-N2 over a wide range of pd show an excellent agreement with the experimentally measured data available in the literature.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

A simple formula is developed to predict the sparking potentials of SF6 and SF6-gas mixture in uniform and non-uniform fields. The formula has been shown to be valid over a very wide range from 1 to 1800 kPa·cm of pressure and electrode gap separation for mixtures containing 5 to 100% SF6. The calculated values are found to be in good agreement with the previously reported measurements in the literature. The formula should aid design engineers in estimating electrode-spacings and clearances in power apparatus and systems.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

Resistivity and dielectric constant are important parameters which influence the separation of particles in a drum-type electrostatic separator. The paper provides details of the measurement of the parameters and data on the magnitude of resistivity and dielectric constant of the minerals of beach sand.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

The experimental results of delay time of a vacuum gap triggered by an exploding wire plasma have been reported. It consists of explosion delay time and propagation delay time. The explosion delay time has been found to be dependent on the parameters of the exploding wire and the exploding wire circuit and is independent of vacuum gap configuration. The propagation delay time depends on the properties of the exploding wire plasma and vacuum gap parameters such as the number of injection slots, gap spacing, gap polarity, etc. In the absence of prebreakdown current in the vacuum gap, the breakdown can be initiated only after the plasma completely bridges the gap spacing. Under this specific condition, it has been shown that the delay time data can be used to calculate the plasma velocity.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

The self-triggering action of the TVG under DC conditions using the same power source as the main circuit is described. Because of the low impedance of the power source compared with the thyratron pulse generator, the TVG can be triggered with voltages as low as 85 V. It is found that circuit conditions influence the minimum stable arc currents that can be sustained.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

Single crystals of tin oxide have been grown under conditions obtained in oil fired porcelain tunnel kilns. It was noted that the reducing conditions in the kilns help in the growth of SnO2 crystals at much lower temperatures (1300°C). The growth seems to more pronounced in presence of silicon carbide. The crystals grow as long fibres of 0.1 to 0.5 mm dia. and 10 to 50 mm length. The crystals exhibit rutile structure and the direction of growth seems to be favoured in any one of the major axes a and c.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

The sparking potentials and swarm coefficients ( ionization and attachment coefficients) were measured in Freon and Freon-air mixtures over the range of 24·3 times 10-16≤ E/ N ≤ 303 times 10-16 V cm2. Addition of Freon increased the sparking potential, and the rate of increase of the attachment coefficient with increasing percentage of Froon in the mixture was much larger than the rate of change of the first ionization coefficient.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

Townsend's primary and secondary ionization coefficients α/p and γ were determined in nitrogen over a wide range of E/p (100-1000 V cm−1 Torr−1) and p (0·4 to 12 Torr at 0 °C) using the pressure variation technique. This technique, along with the Gosseries method of evaluation of ionization coefficients, seems to be more suitable at higher values of E/p, since the errors in these coefficients could be minimized by a suitable selection of p and d, thus eliminating the non-equilibrium ionization condition.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

Salt-fog tests as per International Electrotechnical Commission (IEC) recommendations were conducted on stationtype insulators with large leakage lengths. Later, tests were conducted to simulate natural conditions. From these tests, it was understood that the pollution flashover would occur because of nonuniform pollution layers causing nonuniform voltage distribution during a natural drying-up period. The leakage current during test conditions was very small and the evidence was that the leakage current did not play any significant role in causing flashovers. In the light of the experimental results, some modification of the test procedure is suggested.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

Townsend's primary and secondary ionization coefficients α/p and γ were determined in nitrogen over a wide range of E/p (100-1000 V cm−1 Torr−1) and p (0·4 to 12 Torr at 0 °C) using the pressure variation technique. This technique, along with the Gosseries method of evaluation of ionization coefficients, seems to be more suitable at higher values of E/p, since the errors in these coefficients could be minimized by a suitable selection of p and d, thus eliminating the non-equilibrium ionization condition.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

A simple method for evaluating dielectric relaxation parameters ie given whioh can be used for analyeing the arelaxation times of a liquid into two absorptions.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

An investigation of power frequency (50 Hz) surface partial discharges in dry air, using 21r/3 Rogowski profile electrodes in the low pressure range of 0.067 to 91.333 kPa, shows that for the discharges occurring symmetrically around the electrodes and just outside the uniform field region, the breakdown voltages are 20 to 30% lower than those accounted for by the usual Paschen values. Emphasis, therefore, has been given to modified values of breakdown voltages for any useful calculations. The effect of reduced pressure on inception voltage has been discussed and an attempt has been made to explain the difference between the observed and calculated values on the basis of a pressure-dependent secondary ionization coefficient. It is shown that increasing the insulation thickness in a critical pressure range (0.067 to 0.400 kPa) does not allow any significant increase in the discharge free working stress of the insulation system. At higher pressures (>0.400 kPa) the increase in inception voltage with thickness and pressure follows an equation which is expected to hold for other insulating materials as well.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

The ratio of diffusion coefficient to mobility (D/¿) for electrons has been measured in SF6-air and freon-nitrogen mixtures for various concentrations of SF6 and freon in the mixtures over the range 140¿ E/p¿ 220 V.cm-1 - torr-1. In SF6-air mixtures, the values of D/¿ were always observed to lie intermediate between the values for the pure gases. However, in freon-nitrogen mixtures, with a small concentration (10 percent) of freon in the mixture, the values of D/¿ are found to lie above the boundaries determined by the pure gases. In this mixture, over the lower E/p range (140 to 190) the electrons appear to lose a large fraction of their energy by the excitation of the complex freon molecules, while at higher E/p values (200 to 240), the excitation and consequent deexcitation of nitrogen molecules and its metastables seem to cause an increased rate of ionization of freon molecules.

Relevância:

60.00% 60.00%

Publicador:

Resumo:

A simple triggered vacuum gap has previously been described by the authors in this journal (see ibid., vol.5, 415, 1972). Further studies have resulted in improvement of the performance with regard to sensitivity and consistency of the trigger characteristics and immunity from bridging due to metal particles eroded from the arc. The earlier design suffered from rather frequent bridging of the auxiliary gap and showed rather wide scatter in its trigger characteristics. In the present design thermally stable materials like fused quartz, machinable ceramic 'Supramica 500' (Mycalex Corporation of America), lead titanate, barium titanate (LCC HTD) and silicon carbide have been used to insulate the trigger electrode from the cathode. Consistent triggerings free from bridging, at relatively low voltages of 200-400 V have been obtained.