Theoretical Maximum Limits on Power-Handling Capacity of HVDC Cables
Data(s) |
01/07/2009
|
---|---|
Resumo |
In the case of an ac cable, power transmission is limited by the length of the cable due to the capacitive reactive current component. It is well known that high-voltage direct current (HVDC) cables do not have such limitations. However, insulation-related thermal problems pose a limitation on the power capability of HVDC cables. The author presents a viable theoretical development, a logical extension to Whitehead's theory on thermal limitations of the insulation. The computation of the maximum power-carrying capability of HVDC cables subject to limits on the maximum operable temperature of the insulation is presented. The limitation on the power-carrying capability is closely associated with the electrothermal insulation failure. The effect of environmental interaction by way of external thermal resistance, an important aspect, is also considered in the formulations. The Lagrange multiplier method has been used to handle the ensuing optimization problem. The theory is based on an accepted theory of thermal breakdown in insulation and is an important and a coherent extension of great significance. |
Formato |
application/pdf |
Identificador |
http://eprints.iisc.ernet.in/21844/1/pdf.pdf Reddy, Chandupatla Chakradhar (2009) Theoretical Maximum Limits on Power-Handling Capacity of HVDC Cables. In: IEEE Transactions On Power Delivery, 24 (3). pp. 980-987. |
Publicador |
Ieee-Inst Electrical Electronics Engineers Inc |
Relação |
http://ieeexplore.ieee.org/search/wrapper.jsp?arnumber=5109854 http://eprints.iisc.ernet.in/21844/ |
Palavras-Chave | #Electrical Engineering |
Tipo |
Journal Article PeerReviewed |