Salt-Fog Pollution Test-A Modification to Suit Natural Conditions


Autoria(s): Gopalakrishna, HV; Nandagopal, MR
Data(s)

01/06/1973

Resumo

Salt-fog tests as per International Electrotechnical Commission (IEC) recommendations were conducted on stationtype insulators with large leakage lengths. Later, tests were conducted to simulate natural conditions. From these tests, it was understood that the pollution flashover would occur because of nonuniform pollution layers causing nonuniform voltage distribution during a natural drying-up period. The leakage current during test conditions was very small and the evidence was that the leakage current did not play any significant role in causing flashovers. In the light of the experimental results, some modification of the test procedure is suggested.