The Dissolved Gas Analysis (DGA) a non destructive test procedure, has been in vogue for a long time now, for assessing the status of power and related transformers in service. An early indication of likely internal faults that may exist in Transformers has been seen to be revealed, to a reasonable degree of accuracy by the DGA. The data acquisition and subsequent analysis needs an expert in the concerned area to accurately assess the condition of the equipment. Since the presence of the expert is not always guaranteed, it is incumbent on the part of the power utilities to requisition a well planned and reliable artificial expert system to replace, at least in part, an expert. This paper presents the application of Ordered Ant Mner (OAM) classifier for the prediction of involved fault. Secondly, the paper also attempts to estimate the remaining life of the power transformer as an extension to the elapsed life estimation method suggested in the literature.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Inadvertent failure of power transformers has serious consequences on the power system reliability, economics and the revenue accrual. Insulation is the weakest link in the power transformer prompting periodic inspection of the status of insulation at different points in time. A close Monitoring of the electrical, chemical and such other properties on insulation as are sensitive to the amount of time-dependent degradation becomes mandatory to judge the status of the equipment. Data-driven Diagnostic Testing and Condition Monitoring (DTCM) specific to power transformer is the aspect in focus. Authors develop a Monte Carlo approach for augmenting the rather scanty experimental data normally acquired using Proto-types of power transformers. Also described is a validation procedure for estimating the accuracy of the Model so developed.

Relevância:

100.00% 100.00%

Publicador:

Relevância:

100.00% 100.00%

Publicador:

Resumo:

It is generally known that addition of conducting or insulating particles to mineral transformer oil, lowers its breakdown strength, E-d. However, if the particulates are of molecular dimensions, or nanoparticles, (NPs), as they are called, the breakdown strength is seen to increase considerably. Recent experiments by the authors on oil cooled power equipment such as transformers showed that, nanofluids comprising NPs of selected oxides of iron, such as Fe(3)o(4), called magnetite, added to transformer oil increased the breakdown voltage of the virgin oil and more importantly a remarkable enhancement in the thermal conductivity and the viscosity and hence an increased loadability of the transformer for a given top oil temperature (TOT).

Relevância:

100.00% 100.00%

Publicador:

Resumo:

The presence of moisture in oil impregnated paper insulation (OIP) is detrimental to its long time performance. Until recently, it was thought insulation ageing was only a function of temperature and electrical stress. It has now been realized that moisture in all its forms causes rapid degradation of the electrical and mechanical properties with time. In this study, insulation paper samples were conditioned for desired level of moisture and were impregnated with premium quality transformer oil. The oil impregnated samples with 1 to 3 % moisture content were aged at 90 to 130 C. The indices for determining the extent of ageing considered in this work are degree of polymerization (DP), furan, carbon monoxide and carbon dioxide content. These quantities were monitored throughout the ageing experimental run. End-of-life (EOL) criterion used here is the reduction in the value of DP. Phenomenological models for estimating the service life of insulation are proposed and are validated against actual experimental data.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper presents the application of the on-load exciting current Extended Park's Vector Approach for diagnosing incipient turn-to-turn winding faults in operating power transformers. Experimental and simulated test results demonstrate the effectiveness of the proposed technique, which is based on the spectral analysis of the AC component of the on-load exciting current Park's Vector modulus.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper addresses the subject of condition monitoring and diagnostics of power transformers. The main results of two reliability surveys, carried out under the auspices of CIGRE and IEEE in order to assemble objective data on the performance of transformers in service, are presented, providing useful information on the main causes of transformer failures, the most likely affected components and the related outages times. A survey of the most important methods, actually in use, for condition monitoring and diagnostics of power transformers is also given, which stresses the need for the development of new diagnostic methods, that can be applied without taking the transformers out of service, and that can also provide a fault severity criteria, in particular for determining transformers windings integrity. Preliminary results, concerning the on-going research activity on the development of a new approach for inter-turn winding fault diagnosis in three-phase transformers, are also reported in the paper.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper presents the development and implementation of a digital simulation model of a three-phase, three-leg, power transformer. The proposed model, implemented in MATLAB environment, is based on the physical concept of representing windings as mutually coupled coils, and it is intended to study its adequacy to incorporate, at a later stage, the influences of the occurrence of windings inter- turn short-circuits. Both simulation and laboratory tests results, obtained so far, for a three-phase, 6 kVA transformer, demonstrate the adequacy of the model under normal operating conditions.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper addresses the subject of condition monitoring and diagnostics of power transformers. The main results of two reliability surveys, carried out under the auspices of CIGRE and IEEE in order to assemble objective data on the performance of transformers in service, are presented, providing useful information on the main causes of transformer failures, the most likely affected components and the related outages times. A survey of the most important methods, actually in use, for condition monitoring and diagnostics of power transformers is also given, which stresses the need for the development of new diagnostic methods, that can be applied without taking the transformers out of service, and that can also provide a fault severity criteria, in particular for determining transformers windings integrity. Preliminary results, concerning the on-going research activity on the development of a new approach for inter-turn winding fault diagnosis in three-phase transformers, are also reported in the paper.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper describes the development and the implementation of a multi-agent system for integrated diagnosis of power transformers. The system is divided in layers which contain a number of agents performing different functions. The social ability and cooperation between the agents lead to the final diagnosis and to other relevant conclusions through integrating various monitoring technologies, diagnostic methods and data sources, such as the dissolved gas analysis.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper proposes the application of computational intelligence techniques to assist complex problems concerning lightning in transformers. In order to estimate the currents related to lightning in a transformer, a neural tool is presented. ATP has generated the training vectors. The input variables used in Artificial Neural Networks (ANN) were the wave front time, the wave tail time, the voltage variation rate and the output variable is the maximum current in the secondary of the transformer. These parameters can define the behavior and severity of lightning. Based on these concepts and from the results obtained, it can be verified that the overvoltages at the secondary of transformer are also affected by the discharge waveform in a similar way to the primary side. By using the tool developed, the high voltage process in the distribution transformers can be mapped and estimated with more precision aiding the transformer project process, minimizing empirics and evaluation errors, and contributing to minimize the failure rate of transformers. © 2009 The Berkeley Electronic Press. All rights reserved.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

In this paper we propose a fast and an accurate method for fault diagnosis in power transformers by means of Optimum-Path Forest (OPF) classifier. Since we applied Dissolved Gas Analysis (DGA), the samples have been labeled by IEEE/IEC standard, which was further analyzed by OPF and several other well known supervised pattern recognition techniques. The experiments have showed that OPF can achieve high recognition rates with low computational cost. © 2012 IEEE.