Expert system for the assessment of power transformer insulation condition based on type-2 fuzzy logic systems
Contribuinte(s) |
UNIVERSIDADE DE SÃO PAULO |
---|---|
Data(s) |
18/10/2012
18/10/2012
2011
|
Resumo |
An efficient expert system for the power transformer condition assessment is presented in this paper. Through the application of Duval`s triangle and the method of the gas ratios a first assessment of the transformer condition is obtained in the form of a dissolved gas analysis (DGA) diagnosis according IEC 60599. As a second step, a knowledge mining procedure is performed, by conducting surveys whose results are fed into a first Type-2 Fuzzy Logic System (T2-FLS), in order to initially evaluate the condition of the equipment taking only the results of dissolved gas analysis into account. The output of this first T2-FLS is used as the input of a second T2-FLS, which additionally weighs up the condition of the paper-oil system. The output of this last T2-FLS is given in terms of words easily understandable by the maintenance personnel. The proposed assessing methodology has been validated for several cases of transformers in service. (C) 2010 Elsevier Ltd. All rights reserved. |
Identificador |
EXPERT SYSTEMS WITH APPLICATIONS, v.38, n.7, p.8119-8127, 2011 0957-4174 http://producao.usp.br/handle/BDPI/18167 10.1016/j.eswa.2010.12.153 |
Idioma(s) |
eng |
Publicador |
PERGAMON-ELSEVIER SCIENCE LTD |
Relação |
Expert Systems with Applications |
Direitos |
restrictedAccess Copyright PERGAMON-ELSEVIER SCIENCE LTD |
Palavras-Chave | #Diagnostic reasoning #Knowledge-based systems #Power transformer insulation #Power transformers #Type-2 fuzzy logic systems #Computer Science, Artificial Intelligence #Engineering, Electrical & Electronic #Operations Research & Management Science |
Tipo |
article original article publishedVersion |