996 resultados para Genyk, Timothy
Resumo:
The rapid growth of wind generation in many European countries is pushing power systems into
uncharted territory. As additional wind generators are installed, the changing generation mix may
impact on power system stability. This paper adopts the New England 39 bus system as a test
system for transient stability analysis. Thermal generator models are based on a likely future plant
mix for existing systems, while varying capacities of fixed-speed induction generators (FSIG) and
doubly-fed induction generators (DFIG) are considered. The main emphasis here has been placed
on the impact of wind technology mix on inter-area oscillations following transient grid
disturbances. In addition, both rotor angle stability and transient voltage stability are examined, and
results are compared with current grid code requirements and standards. Results have shown that
FSIGs can reduce tie-line oscillations and improve damping following a transient disturbance, but
they also cause voltage stability and rotor angle stability problems at high wind penetrations. In
contrast, DFIGs can improve both voltage and rotor angle stability, but their power output
noticeably oscillates during disturbances.
Resumo:
This paper studies the impact of tower shadow effect on the power output of a fixed-speed wind farm. A data acquisition unit was placed at a wind farm in Northern Ireland which consists of ten fixed-speed wind turbines. The recording equipment logged the wind farmpsilas electrical data, which was time stamped using the global positioning network. Video footage of the wind farm was recorded and from it the blade angle of each turbine was determined with respect to time. Using the blade angle data and the wind farmpsilas power output, studies where performed to ascertain the extent of tower shadow effect on power fluctuation. This paper presents evidence that suggests that tower shadow effect has a significant impact on power fluctuation and that this effect is increased due to the synchronising of turbine blades around the tower region.
Resumo:
This paper presents transient stability analysis for a power system with high wind penetration. The transient stability has been evaluated based on two stability criteria: rotor angle stability and voltage stability. A modified IEEE-14 bus system has been used as the main study network and simulations have been conducted at several wind power penetration levels, defined as a fraction of total system generation. A wide range of scenarios have been presented based on the wind farm voltage at the point of connection, i.e. low voltage (LV) distribution level and high voltage (HV) transmission level, and the type of wind generator technology, i.e. fixed speed induction generator (FSIG) and doubly-fed induction generator (DFIG).
Resumo:
This paper proposes a fast moving window algorithm for QR and Cholesky decompositions by simultaneously applying data updating and downdating. The developed procedure is based on inner products and entails a similar downdating to that of the Chambers’ approach. For adding and deleting one row of data from the original matrix, a detailed analysis shows that the proposed algorithm outperforms existing ones in terms or computational efficiency, if the number of columns exceeds 7. For a large number of columns, the proposed algorithm is numerically superior compared to the traditional sequential technique.
Resumo:
his paper proposes an optimisation-based method to calculate the critical slip (speed) of dynamic stability and critical clearing time (CCT) of a self-excited induction generator (SEIG). A simple case study using the Matlab/Simulink environment has been included to exemplify the optimisation method. Relationships between terminal voltage, critical slip and reactance of transmission line, CCT and inertial constant have been determined, based on which analysis of impact on relaying setting has been further conducted for another simulation case.
Resumo:
A reduction in the time required to locate and restore faults on a utility's distribution network improves the customer minutes lost (CML) measurement and hence brings direct cost savings to the operating company. The traditional approach to fault location involves fault impedance determination from high volume waveform files dispatched across a communications channel to a central location for processing and analysis. This paper examines an alternative scheme where data processing is undertaken locally within a recording instrument thus reducing the volume of data to be transmitted. Processed event fault reports may be emailed to relevant operational staff for the timely repair and restoration of the line.
Resumo:
This paper considers the enhancement of loss-of-mains detection by use of a differential rate-of-change-of-frequency relay to reduce nuisance tripping and improve sensitivity to small excursions in frequency. The telecommunications media which might carry the differential ROCOF signal are reviewed with a focus on channel latency, bandwidth and security.
Resumo:
This paper discusses methods of using the Internet as a communications media between distributed generator sites to provide new forms of loss-of-mains protection. An analysis of the quality of the communications channels between several nodes on the network was carried out experimentally. It is shown that Internet connections in urban environments are already capable of providing real-time power system protection, whilst rural Internet connections are borderline suitable but could not yet be recommended as a primary method of protection. Two strategies of providing loss-of-mains across Internet protocol are considered, broadcast of a reference frequency or phasor representing the utility and an Internet based inter-tripping scheme.
Resumo:
This paper studies the system modelling and control aspects of switched reluctance generator (SRG) based variable speed wind turbines. A control system is implemented to provide proper operation of the SRG as well as power tracking capabilities for varying wind speeds. The control system for the grid side inverter that will allow the SRG to properly generate power to the system is also presented. Studies are presented of both the SRG and inverter control systems capabilities during a balanced three-phase fault. The paper will demonstrate that the SRG based wind turbine presents a feasible variable wind speed solution with good fault response capabilities.
Resumo:
This paper proposes a method to assess the small signal stability of a power system network by selective determination of the modal eigenvalues. This uses an accelerating polynomial transform, designed using approximate eigenvalues
obtained from a wavelet approximation. Application to the IEEE 14 bus network model produced computational savings of 20%,over the QR algorithm.
Resumo:
The impact of power fluctuations arising from fixed-speed wind turbines on the magnitude and frequency of inter-area oscillations has been investigated. The authors introduced data acquisition equipment to record the power flow on the interconnector between the Northern Ireland and Republic of Ireland systems. Through monitoring the interconnector oscillation using a fast Fourier transform, it was possible to determine the magnitude and frequency of the inter-area oscillation between the two systems. The impact of tower shadow on the output power from a wind farm was analysed using data recorded on site. A case study investigates the effect on the system of the removal of a large fixed-speed wind farm. Conclusions are drawn on the impact that conventional generation and the output from fixed-speed wind farms have on the stability of the Irish power system.
Resumo:
The impact of power fluctuations arising from fixed-speed wind turbines on the magnitude and frequency of inter-area oscillations was investigated. The authors used data acquisition equipment to record the power flow on the interconnector between the Northern Ireland and Republic of Ireland systems. By monitoring the interconnector oscillation using a fast Fourier transform, it was possible to determine the magnitude and frequency of the inter-area oscillation between the Northern Ireland electricity system and that of the electricity supply board. Analysis was preformed to determine the relationship (if any) between the inter-area oscillation and the observed wind power generation at the corresponding time. Subsequently, regression analysis was introduced to model this relationship between the FFT output and the wind power generation. The effect of conventional generators on the magnitude and frequency of the inter-area oscillation was also considered.
Resumo:
This paper introduces an algorithm that calculates the dominant eigenvalues (in terms of system stability) of a linear model and neglects the exact computation of the non-dominant eigenvalues. The method estimates all of the eigenvalues using wavelet based compression techniques. These estimates are used to find a suitable invariant subspace such that projection by this subspace will provide one containing the eigenvalues of interest. The proposed algorithm is exemplified by application to a power system model.
Resumo:
The inertia of fixed-speed wind turbine generators (WTGs) helps to mitigate under-frequency transients, promotes fault ride-through and damps inter-area oscillations. It is therefore important to quantify this inertia. The authors use measured wind farm responses during under-frequency transients to provide this information. They discuss the extent of the data and the criteria used to select certain events for further analysis. The estimation of WTG inertia is based on a induction generator model. The basis of the model will be described. The manner in which the model is applied to estimate the inertia from the measured data is then explained. Finally, the implications of the results for power system operation are assessed.
Resumo:
Frequency stability has not necessarily been a major problem for the majority of power systems in the past. However, for economic and environmental reasons, power systems are now operated closer to stability limits to maximise the use of the existing networks. Therefore, introduction of new, more efficient and renewable generation technologies, and their effect on the power system must be fully understood if a reliable and secure electricity supply is to be maintained. Using the Northern Ireland, and interconnected Republic of Ireland electricity networks as a case study, this paper addresses some of the issues regarding integration and modelling of combined cycle gas turbines (CCGT), and wind turbine generator (WTG) technology on a small islanded power system.