438 resultados para mediumfrequency transformer


Relevância:

10.00% 10.00%

Publicador:

Resumo:

In this work a detailed modeling of three-phase distribution transformers aimed at complementing well-known approaches is presented. Thus, incidence of angular displacement and tapping is taken into account in the proposed models, considering both actual values and per unit. The analysis is based on minimal data requirement: solely short-circuit admittance is needed since three-phase transformers are treated as non-magnetically-coupled single-phase transformers. In order to support the proposed methodology, results obtained through laboratory tests are presented.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

This article presents a new approach to minimize the losses in electrical power systems. This approach considers the application of the primal-dual logarithmic barrier method to voltage magnitude and tap-changing transformer variables, and the other inequality constraints are treated by augmented Lagrangian method. The Lagrangian function aggregates all the constraints. The first-order necessary conditions are reached by Newton's method, and by updating the dual variables and penalty factors. Test results are presented to show the good performance of this approach.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A robust 12 kW rectifier with low THD in the line currents, based on an 18-pulse transformer arrangement with reduced kVA capacities followed by a high-frequency isolation stage is presented in this work. Three full-bridge (buck-based) converters are used to allow galvanic isolation and to balance the dc-link currents, without current sensing or current controller. The topology provides a regulated dc output with a very simple and well-known control strategy and natural three-phase power factor correction. The phase-shift PWM technique, with zero-voltage switching is used for the high-frequency dc-dc stage. Analytical results from Fourier analysis of winding currents and the vector diagram of winding voltages are presented. Experimental results from a 12 kW prototype are shown in the paper to verify the efficiency, robustness and simplicity of the command circuitry to the proposed concept.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A constant-current stimulator for high-impedance loads using only low-cost standard high-voltage components Is presented. A voltage-regulator powers an oscillator built across the primary of a step-up transformer whose secondary supplies, after rectification, the high voltage to a switched current-mirror in the driving stage. Adjusting the regulated voltage controls the pulsed-current intensity. A prototype produces stimulus of amplitude and pulsewidth within 0 less than or equal to I-skin less than or equal to 20 mA and 50 mus less than or equal to T-pulse less than or equal to 1 ms, respectively. Pulse-repetition spans from 1 Hz to 10 Hz. Worst case ripple is 3.7% at I-skin = 1 mA. Overall consumption is 5.6 W at I-skin = 20 mA.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

This paper presents a new approach to solve the Optimal Power Flow problem. This approach considers the application of logarithmic barrier method to voltage magnitude and tap-changing transformer variables and the other constraints are treated by augmented Lagrangian method. Numerical test results are presented, showing the effective performance of this algorithm. (C) 2005 Elsevier Ltd. All rights reserved.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

Large scale combinatorial problems such as the network expansion problem present an amazingly high number of alternative configurations with practically the same investment, but with substantially different structures (configurations obtained with different sets of circuit/transformer additions). The proposed parallel tabu search algorithm has shown to be effective in exploring this type of optimization landscape. The algorithm is a third generation tabu search procedure with several advanced features. This is the most comprehensive combinatorial optimization technique available for treating difficult problems such as the transmission expansion planning. The method includes features of a variety of other approaches such as heuristic search, simulated annealing and genetic algorithms. In all test cases studied there are new generation, load sites which can be connected to an existing main network: such connections may require more than one line, transformer addition, which makes the problem harder in the sense that more combinations have to be considered.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

The paper describes a novel neural model to estimate electrical losses in transformer during the manufacturing phase. The network acts as an identifier of structural features on electrical loss process, so that output parameters can be estimated and generalized from an input parameter set. The model was trained and assessed through experimental data taking into account core losses, copper losses, resistance, current and temperature. The results obtained in the simulations have shown that the developed technique can be used as an alternative tool to make the analysis of electrical losses on distribution transformer more appropriate regarding to manufacturing process. Thus, this research has led to an improvement on the rational use of energy.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A bifilar Bi-2212 bulk coil with parallel shunt resistor was tested under fault current condition using a 3 MVA single-phase transformer in a 220 V-60 Hz line achieving fault current peak of 8 kA. The fault current tests are performed from steady state peak current of 200 A by applying controlled short circuits up to 8 kA varying the time period from one to six cycles. The test results show the function of the shunt resistor providing homogeneous quench behavior of the HTS coil besides its intrinsic stabilizing role. The limiting current ratio achieves a factor 4.2 during 5 cycles without any degradation.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

The performance of the three-phase core type transformers, under AC/DC double excitation is discussed in this work. It is presented a mathematical model that considers the mutual coupling between phases and the magnetic nonlinearity. The validity of the proposed model is verified by means of the experimental and simulated results.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

This work presents a new high power factor three-phase rectifier based on a Y-connected differential autotransformer with reduced kVA and 18-pulse input current followed by three DC-DC boost converters. The topology provides a regulated output voltage and natural three-phase input power factor correction. The lowest input current harmonic components are the 17th and the 19th. Three boost converters, with constant input currents and regulated parallel connected output voltages are used to process 4kW each one. Analytical results from Fourier analyses of winding currents and the vector diagram of winding voltages are presented. Simulation results to verify the proposed concept and experimental results are shown in the paper.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

This work proposes a new isolated high power factor 12kW power supply based on an 18-pulse transformer arrangement. Three full-bridge converters are used for isolation and to balance the DC-link currents, without current sensing or a current controller. The topology provides a regulated DC output with a very simple control strategy. Simulation and experimental results are presented in this paper.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A simple constant-current electrocutaneous stimulator for high-impedance loads using low-cost, standard high-voltage components is presented. A voltage-regulator powers an oscillator built across the primary of a transformer whose secondary delivers, after rectification, the high-voltage supply to switched current-mirrors in the driving stage. Since the compliance high-voltage is proportional to the stimulation current, overall power consumption is minimized. By adjusting the regulated voltage, control of the pulsed-current amplitude is achieved. A prototype with readily available components features stimulation currents of amplitude and pulsewidth in the range 0≤Iskin≤20mA and 50μs ≤Tpulse≤1ms, respectively. Pulse-repetition spans from 1 Hz to 10Hz. Worst-case ripple is 3.7% @Iskin=1mA. Measured pulse fall-time is shorter than 32μs. Overall consumption is 4.4W @Iskin=20mA. Subject isolation from line is 4KV.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A new approach to solving the Optimal Power Flow problem is described, making use of some recent findings, especially in the area of primal-dual methods for complex programming. In this approach, equality constraints are handled by Newton's method inequality constraints for voltage and transformer taps by the logarithmic barrier method and the other inequality constraints by the augmented Lagrangian method. Numerical test results are presented, showing the effective performance of this algorithm. © 2001 IEEE.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

In this paper a method for solving the Short Term Transmission Network Expansion Planning (STTNEP) problem is presented. The STTNEP is a very complex mixed integer nonlinear programming problem that presents a combinatorial explosion in the search space. In this work we present a constructive heuristic algorithm to find a solution of the STTNEP of excellent quality. In each step of the algorithm a sensitivity index is used to add a circuit (transmission line or transformer) to the system. This sensitivity index is obtained solving the STTNEP problem considering as a continuous variable the number of circuits to be added (relaxed problem). The relaxed problem is a large and complex nonlinear programming and was solved through an interior points method that uses a combination of the multiple predictor corrector and multiple centrality corrections methods, both belonging to the family of higher order interior points method (HOIPM). Tests were carried out using a modified Carver system and the results presented show the good performance of both the constructive heuristic algorithm to solve the STTNEP problem and the HOIPM used in each step.