11 resultados para transformers

em University of Queensland eSpace - Australia


Relevância:

20.00% 20.00%

Publicador:

Resumo:

This paper investigates the effective diagnostic technique(s) for assessing the condition of insulation in aged power transformers. A number of electrical, mechanical and chemical techniques were investigated. Many of these techniques are already used by the utility engineers and two comparatively new techniques are proposed in this paper. Results showing the effectiveness of these diagnostics are presented and correlation between the techniques are also presented. Finally, merits and suitability of different techniques are discussed in this paper.

Relevância:

20.00% 20.00%

Publicador:

Resumo:

This paper describes the application of two relatively new diagnostic techniques for the determination of insulation condition in aged transformers. The techniques are (a) measurements of interfacial polarization spectra by a DC method and (b) measurements of molecular weight and its distribution by gel permeation chromatography. Several other electrical properties of the cellulose polymer were also investigated. Samples were obtained from a retired power transformer and they were analysed by the developed techniques. Six distribution transformers were also tested with the interfacial polarization spectra measurement technique, and the molecular weight of paper/pressboard samples from these transformers were also measured by the gel permeation chromatography. The variation of the results through different locations in a power transformer is discussed in this paper. The possible correlation between different measured properties was investigated and discussed in this paper.

Relevância:

20.00% 20.00%

Publicador:

Resumo:

This paper describes the analysis of accelerated aged insulation samples to investigate the degradation processes observed in the insulation from aged transformers. Short term accelerated ageing experiments were performed on paper wrapped insulated conductors and on pressboard samples. The condition of aged insulation samples was investigated by two relatively new diagnostic techniques: (a) measurements of interfacial polarization spectra by a DC method (b) measurements of molecular weight and its distribution by gel permeation chromatography. Several other electrical properties of the paper/pressboard samples were also studied. Possible correlations have been investigated among the different measured properties. The GPC results have been used to predict how molecular weights change with temperature and time.

Relevância:

20.00% 20.00%

Publicador:

Resumo:

This paper presents a review of the time-domain polarization measurement techniques for the condition assessment of aged transformer insulation. The polarization process is first described with appropriate dielectric response theories and then commonly used polarization methods are described with special emphasis on the most widely used return voltage(rv) measurement. Most recent emphasis has been directed to techniques of determining moisture content of insulation indirectly by measuring rv parameters. The major difficulty still lies with the accurate interpretation of return voltage results. This paper investigates different thoughts regarding the interpretation of rv results for different moisture and ageing conditions. Other time domain polarization measurement techniques and their results are also presented in this paper.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

In order to effectively suppress the noise radiation from large electrical power transformers, both the structure-borne and air-borne sound fields need to be characterised. The characterisation can be made either from theoretical predictions or by in-situ measurements. This paper presents the study of the sound radiation from a large power transformer in a substation. The radiation pattern can be predicted from the measured acceleration distribution and the predicted value is not affected by other noise sources. Alternatively, the farfield sound pressure level can be predicted from the sound pressure level measured at NEMA locations. Both the near- and far-field power radiation can be in-situ measured using the sound intensity technique. It is shown that both the vibration of a transformer tank wall and the radiated noise consist of a series of tonal components mainly at the first few harmonic frequencies of 100 Hz. Also, the neglect of the noise radiation from the transformer (top and bottom) lids does not affects the accuracy of the transformer radiation characterisation. (C) 1998 Elsevier Science Ltd. All rights reserved.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

The equipment used to measure magnetic fields and, electric currents in residences is described. The instrumentation consisted of current transformers, magnetic field probes and locally designed and, built signal conditioning modules. The data acquisition system was capable of unattended recording for extended time periods. The complete system was calibrated to verify its response to known physical inputs. (C) 2003 ISA-The Instrumentation Automation Society.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

High-level language program compilation strategies can be proven correct by modelling the process as a series of refinement steps from source code to a machine-level description. We show how this can be done for programs containing recursively-defined procedures in the well-established predicate transformer semantics for refinement. To do so the formalism is extended with an abstraction of the way stack frames are created at run time for procedure parameters and variables.

Relevância:

10.00% 10.00%

Publicador: