Electrical and chemical diagnostics of transformers insulation .A. Aged transformer samples
Data(s) |
01/01/1997
|
---|---|
Resumo |
This paper describes the application of two relatively new diagnostic techniques for the determination of insulation condition in aged transformers. The techniques are (a) measurements of interfacial polarization spectra by a DC method and (b) measurements of molecular weight and its distribution by gel permeation chromatography. Several other electrical properties of the cellulose polymer were also investigated. Samples were obtained from a retired power transformer and they were analysed by the developed techniques. Six distribution transformers were also tested with the interfacial polarization spectra measurement technique, and the molecular weight of paper/pressboard samples from these transformers were also measured by the gel permeation chromatography. The variation of the results through different locations in a power transformer is discussed in this paper. The possible correlation between different measured properties was investigated and discussed in this paper. |
Identificador | |
Idioma(s) |
eng |
Palavras-Chave | #Engineering, Electrical & Electronic |
Tipo |
Journal Article |