2 resultados para energized shield wire line
em Biblioteca Digital da Produção Intelectual da Universidade de São Paulo
Resumo:
This paper presents an analysis of the impact of the lightning overvoltages on the operational performance of the energized shield wire line technology (SWL) implemented in two locations of the State of Rondonia, Brazil. The analysis covers the periods of 1996 to 2000 (SWL Jaru) and 1997 to 2002 (SWL Itapua do Oeste), and shows that lightning is responsible for most of the system outages. The paper describes the satisfactory results achieved with the system, showing that the isolation and energization of the shield wires does not deteriorate the lightning performance of the 230 kV transmission lines. Comparisons between the performances of the SWL technology, conventional 34.5 kV lines, and thermal power plants in operation in the same region are also presented. The results demonstrate the technical and economical viability of the SWL technology and show that its application can lead to a postponement of investments.
Resumo:
In recent years, there was an increase of ancillary service loads, such as signaling systems, inspection robots, surveillance cameras, and other monitoring devices distributed along high-voltage transmission lines which require low-power dc voltage supplies. This paper investigates the use of the induced voltage in the shield wires of an overhead 525 kV transmission line as a primary power source. Since phase current variations throughout the day affect the induced voltage in the overhead ground wire, a step-down dc-dc converter is used after rectification of the ac voltage to provide a regulated dc output voltage. The initial encouraging results obtained indicate that this form of power supply can be a feasible and cost-effective alternative for feeding small ancillary service loads. The simulation results are validated by field measurements as well as the installation of a 200 W voltage stabilization system prototype.