Nondetection Index of Anti-Islanding Passive Protection of Synchronous Distributed Generators


Autoria(s): Salles, Diogo; Freitas, Walmir; Vieira, Jose C. M.; Xu, Wilsun
Contribuinte(s)

UNIVERSIDADE DE SÃO PAULO

Data(s)

05/11/2013

05/11/2013

2012

Resumo

Synchronous distributed generators are prone to operate islanded after contingencies, which is usually not allowed due to safety and power-quality issues. Thus, there are several anti-islanding techniques; however, most of them present technical limitations so that they are likely to fail in certain situations. Therefore, it is important to quantify and determine whether the scheme under study is adequate or not. In this context, this paper proposes an index to evaluate the effectiveness of anti-islanding frequency-based relays commonly used to protect synchronous distributed generators. The method is based on the calculation of a numerical index that indicates the time period that the system is unprotected against islanding considering the global period of analysis. Although this index can precisely be calculated based on several electromagnetic transient simulations, a practical method is also proposed to calculate it directly from simple analytical formulas or lookup tables. The results have shown that the proposed approach can assist distribution engineers to assess and set anti-islanding protection schemes.

Natural Resources Canada, Canada

Natural Resources Canada, Canada

FAPESP

FAPESP

CNPq (Brazil)

CNPq, Brazil

Identificador

IEEE TRANSACTIONS ON POWER DELIVERY, PISCATAWAY, v. 27, n. 3, supl. 4, Part 1, pp. 1509-1518, JUL, 2012

0885-8977

http://www.producao.usp.br/handle/BDPI/41834

10.1109/TPWRD.2012.2190624

http://dx.doi.org/10.1109/TPWRD.2012.2190624

Idioma(s)

eng

Publicador

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

PISCATAWAY

Relação

IEEE TRANSACTIONS ON POWER DELIVERY

Direitos

restrictedAccess

Copyright IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

Palavras-Chave #DISTRIBUTED GENERATION #DISTRIBUTION SYSTEM #ISLANDING #NONDETECTION ZONE #SYNCHRONOUS GENERATOR #RELAYS #PERFORMANCE #SYSTEMS #ENGINEERING, ELECTRICAL & ELECTRONIC
Tipo

article

original article

publishedVersion