6 resultados para SFCL


Relevância:

20.00% 20.00%

Publicador:

Resumo:

The resistive-type superconducting fault current limiters (RSFCL) prototypes using YBCO-coated conductors have shown current limitation for medium voltage class applications for acting time up to 80 ms. By connecting an air-core reactor in parallel with the RSFCL, thus making an hybrid current limiter, one can extend the acting time for up to 1 s. In this work, we report the performance of a hybrid current limiter subjected to an AC peak fault current of 2 kA during 1 s for which within the first 80 ms the SFCL limits the current concurrently with the air-core reactor, and for the remaining 920 ms, only the air-core reactor limits the current. In order to evaluate the actual conditions for subsequent reconnection of RSFCL to the power grid, the hybrid fault current limiter was tested varying the time interval for recovery from 900 ms and 1.2 s, followed again by the concurrent operation of the hybrid limiter during 1 s (SFCL during 80 ms). From this evaluation test, the recovery time can be measured and compared using the voltage peak generated in superconducting module from the first and second fault test. The recovery time was also determined through the pulsed current method (PCM) on short-length sample test. The results showed that the fault current was limited from 1.9 kA down to 514 A after 1 cycle of 60 Hz frequency, with recovery time lower than 1.2 s for two subsequent fault current tests.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A modular superconducting fault current limiter (SFCL) consisting of 16 elements was constructed and tested in a 220 V line for a fault current between 1 kA to 7.4 kA. The elements are made up of second generation (2G) YBCO-coated conductor tapes with stainless steel reinforcement. For each element four tapes were electrically connected in parallel with effective length of 0.4 m per element, totaling 16 elements connected in series. The evaluation of SFCL performance was carried out under DC and AC tests. The DC test was performed through pulsed current tests and its recovery characteristics under load current were analysed by changing the shunt resistor value. The AC test performed using a 3 MVA/220 V/60 Hz transformer has shown the current limiting ratio achieved a factor higher than 10 during fault of up to five cycles without conductor degradation. The measurement of the voltage for each element during the AC test showed that in this modular SFCL the quench is homogeneous and the transition occurs similarly in all the elements.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

Fundação de Amparo à Pesquisa do Estado de São Paulo (FAPESP)

Relevância:

10.00% 10.00%

Publicador:

Resumo:

A single-phase superconducting fault current limiter (SFCL) using a 0.9 m length of YBCO coated conductor (CC) tape was tested in 220 V-60 Hz line for fault current up to 1 kA, operating in 77 K. In this work are presented the IN experimental curves measured under DC and AC currents for the electrical characterization of the CC tape in order to design a low voltage current limiter. The experimental setup is described and the test results are presented for a unit conducting a steady nominal AC current of 50 A and also during the fault time (I to 5 cycles.) the performance of the CC-based SFCL providing the limiting resistance developed in the whole tape length after few milliseconds of the beginning of the fault was analyzed.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

In this work, we report on the evaluation of a superconducting fault current limiter (SFCL). It is consisted of a modular superconducting device combined with a short-circuited transformer with a primary copper winding connected in series to the power line and the secondary side short-circuited by the superconducting device. The basic idea is adding a magnetic component to contribute to the current limitation by the impedance reflected to the line after transition of the superconducting device. The evaluation tests were performed with a prospective current up to 2 kA, with the short-circuited transformer of 2.5 kVA, 220 V/660 V connected to a test facility of 100 kVA power capacity. The resistive SFCL using a modular superconducting device was tested without degradation for a prospective fault current of 1.8 kA, achieving the limiting factor 2.78; the voltage achieved 282 V corresponding to an electric field of 11 V/m. The test performed with the combined SFCL (xsuperconducting device + transformer) using series and toroidal transformers showed current limiting factor of 3.1 and 2 times, respectively. The test results of the combined SFCL with short-circuited transformer showed undesirable influence of the transformer impedance, resulting in reduction of the fault current level. © 2002-2011 IEEE.

Relevância:

10.00% 10.00%

Publicador:

Resumo:

The thesis topic concerns the limitation of fault current high temperature superconducting (HTS), reported in scientific literature by the acronym HTSFCL (High Temperature Superconducting Fault Current Limiter) or more commonly with SFCL. These devices, at least in their ideal concept, turn on limiting short-circuit current only when the event of failure occurs, and are transparent to the network during normal operating conditions. The thesis is therefore focused on the study of diff�erent types of SFCL and results in the production of a new and original concept of superconducting limiter, called "DC Resistive SFCL". It has designed and patented in the Department of Electrical Engineering University of Bologna. The author and ing. Antonio Morandi (tutor) are the inventors. The objective of the thesis is therefore to propose a type of SFCL which may have the potential to be a viable economic solution as well as technique. The innovative concept of DC Resistive SFCL device, in fact, provides a DC operating conditions for the used superconducting (SC). It allows the use of cryogen-free solutions for cooling system and the exploitation of cheap SC materials (MgB2), both of reality are already commercially existing and indeed precluded by the types of SFCL which provides an AC operating conditions for the used SC material.