em Aston University Research Archive


Relevância:

30.00% 30.00%

Publicador:

Resumo:

A long period grating (LPG) written in a standard optical fibre was modified by using a femtosecond laser to induce an asymmetric change in the cladding's refractive index. This device produced blue and red wavelength shifts depending on the orientation of applied curvature, with maximum sensitivities of -1.6 nm m and +3.8 nm m, suggesting that this type of LPG may be useful as a shape sensor.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

We report on an optical bend sensor based on a Bragg grating inscribed in an eccentric core polymer optical fiber. The device exhibits the strong fiber orientation dependence, the wide bend curvature range of ± 22.7 m-1 and high bend sensitivity of 63 pm/m-1.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

This thesis first considers the calibration and signal processing requirements of a neuromagnetometer for the measurement of human visual function. Gradiometer calibration using straight wire grids is examined and optimal grid configurations determined, given realistic constructional tolerances. Simulations show that for gradiometer balance of 1:104 and wire spacing error of 0.25mm the achievable calibration accuracy of gain is 0.3%, of position is 0.3mm and of orientation is 0.6°. Practical results with a 19-channel 2nd-order gradiometer based system exceed this performance. The real-time application of adaptive reference noise cancellation filtering to running-average evoked response data is examined. In the steady state, the filter can be assumed to be driven by a non-stationary step input arising at epoch boundaries. Based on empirical measures of this driving step an optimal progression for the filter time constant is proposed which improves upon fixed time constant filter performance. The incorporation of the time-derivatives of the reference channels was found to improve the performance of the adaptive filtering algorithm by 15-20% for unaveraged data, falling to 5% with averaging. The thesis concludes with a neuromagnetic investigation of evoked cortical responses to chromatic and luminance grating stimuli. The global magnetic field power of evoked responses to the onset of sinusoidal gratings was shown to have distinct chromatic and luminance sensitive components. Analysis of the results, using a single equivalent current dipole model, shows that these components arise from activity within two distinct cortical locations. Co-registration of the resulting current source localisations with MRI shows a chromatically responsive area lying along the midline within the calcarine fissure, possibly extending onto the lingual and cuneal gyri. It is postulated that this area is the human homologue of the primate cortical area V4.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

The diagnosis of ocular disease is increasingly important in optometric practice and there is a need for cost effective point of care assays to assist in that. Although tears are a potentially valuable source of diagnostic information difficulties associated with sample collection and limited sample size together with sample storage and transport have proved major limitations. Progressive developments in electronics and fibre optics together with innovation in sensing technology mean that the construction of inexpensive point of care fibre optic sensing devices is now possible. Tear electrolytes are an obvious family of target analytes, not least to complement the availability of devices that make the routine measurement of tear osmolarity possible in the clinic. In this paper we describe the design, fabrication and calibration of a fibre-optic based electrolyte sensor for the quantification of potassium in tears using the ex vivo contact lens as the sample source. The technology is generic and the same principles can be used in the development of calcium and magnesium sensors. An important objective of this sensor technology development is to provide information at the point of routine optometric examination, which would provide supportive evidence of tear abnormality.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

We present an optical bend sensor based on a Bragg grating written in an eccentric core polymer optical fibre. The grating wavelength shifts are studied as a function of bend curvature and fibre orientation and the device exhibits strong fibre orientation dependence, wide bend curvature range of ± 22.7 m-1 and high bend sensitivity of 63 pm/m-1, which is 80 times higher than the reported sensor based on an offset-FBG in standard single mode silica fibre.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

A long period grating (LPG) written in a standard optical fibre was modified by using a femtosecond laser to induce an asymmetric change in the cladding's refractive index. This device produced blue and red wavelength shifts depending on the orientation of applied curvature, with maximum sensitivities of -1.6 nm m and +3.8 nm m, suggesting that this type of LPG may be useful as a shape sensor.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

Long period grating was UV inscribed into a multicore fiber consisting of 120 single mode cores. The multicore fiber that hosts the grating was fusion spliced into a single mode fiber at both ends. The splice creates a taper transition between the two types of fiber that produces a nonadiabatic mode evolution; this results in the illumination of all the modes in the multicore fiber. The spectral characteristics of this fiber device as a function of curvature were investigated. The device yielded a significant spectral sensitivity as high as 1.23 nm/m-1 and 3.57 dB/m-1 to the ultra-low curvature values from 0 to 1 m-1. This fiber device can also distinguish the orientation of curvature experienced by the fiber as the long period grating attenuation bands producing either a blue or red wavelength shift. The finite element method (FEM) model was used to investigate the modal behavior in multicore fiber and to predict the phase-matching curves of the long period grating inscribed into multicore fiber. © 2014 Optical Society of America.

Relevância:

30.00% 30.00%

Publicador:

Resumo:

This study extends a previous research concerning intervertebral motion registration by means of 2D dynamic fluoroscopy to obtain a more comprehensive 3D description of vertebral kinematics. The problem of estimating the 3D rigid pose of a CT volume of a vertebra from its 2D X-ray fluoroscopy projection is addressed. 2D-3D registration is obtained maximising a measure of similarity between Digitally Reconstructed Radiographs (obtained from the CT volume) and real fluoroscopic projection. X-ray energy correction was performed. To assess the method a calibration model was realised a sheep dry vertebra was rigidly fixed to a frame of reference including metallic markers. Accurate measurement of 3D orientation was obtained via single-camera calibration of the markers and held as true 3D vertebra position; then, vertebra 3D pose was estimated and results compared. Error analysis revealed accuracy of the order of 0.1 degree for the rotation angles of about 1mm for displacements parallel to the fluoroscopic plane, and of order of 10mm for the orthogonal displacement. © 2010 P. Bifulco et al.