2 resultados para Equipment testing
em Digital Commons - Michigan Tech
Resumo:
Transformers are very important elements of any power system. Unfortunately, they are subjected to through-faults and abnormal operating conditions which can affect not only the transformer itself but also other equipment connected to the transformer. Thus, it is essential to provide sufficient protection for transformers as well as the best possible selectivity and sensitivity of the protection. Nowadays microprocessor-based relays are widely used to protect power equipment. Current differential and voltage protection strategies are used in transformer protection applications and provide fast and sensitive multi-level protection and monitoring. The elements responsible for detecting turn-to-turn and turn-to-ground faults are the negative-sequence percentage differential element and restricted earth-fault (REF) element, respectively. During severe internal faults current transformers can saturate and slow down the speed of relay operation which affects the degree of equipment damage. The scope of this work is to develop a modeling methodology to perform simulations and laboratory tests for internal faults such as turn-to-turn and turn-to-ground for two step-down power transformers with capacity ratings of 11.2 MVA and 290 MVA. The simulated current waveforms are injected to a microprocessor relay to check its sensitivity for these internal faults. Saturation of current transformers is also studied in this work. All simulations are performed with the Alternative Transients Program (ATP) utilizing the internal fault model for three-phase two-winding transformers. The tested microprocessor relay is the SEL-487E current differential and voltage protection relay. The results showed that the ATP internal fault model can be used for testing microprocessor relays for any percentage of turns involved in an internal fault. An interesting observation from the experiments was that the SEL-487E relay is more sensitive to turn-to-turn faults than advertized for the transformers studied. The sensitivity of the restricted earth-fault element was confirmed. CT saturation cases showed that low accuracy CTs can be saturated with a high percentage of turn-to-turn faults, where the CT burden will affect the extent of saturation. Recommendations for future work include more accurate simulation of internal faults, transformer energization inrush, and other scenarios involving core saturation, using the newest version of the internal fault model. The SEL-487E relay or other microprocessor relays should again be tested for performance. Also, application of a grounding bank to the delta-connected side of a transformer will increase the zone of protection and relay performance can be tested for internal ground faults on both sides of a transformer.
Resumo:
Increasing prices for fuel with depletion and instability in foreign oil imports has driven the importance for using alternative and renewable fuels. The alternative fuels such as ethanol, methanol, butyl alcohol, and natural gas are of interest to be used to relieve some of the dependence on oil for transportation. The renewable fuel, ethanol which is made from the sugars of corn, has been used widely in fuel for vehicles in the United States because of its unique qualities. As with any renewable fuel, ethanol has many advantages but also has disadvantages. Cold startability of engines is one area of concern when using ethanol blended fuel. This research was focused on the cold startability of snowmobiles at ambient temperatures of 20 °F, 0 °F, and -20 °F. The tests were performed in a modified 48 foot refrigerated trailer which was retrofitted for the purpose of cold-start tests. Pure gasoline (E0) was used as a baseline test. A splash blended ethanol and gasoline mixture (E15, 15% ethanol and 85% gasoline by volume) was then tested and compared to the E0 fuel. Four different types of snowmobiles were used for the testing including a Yamaha FX Nytro RTX four-stroke, Ski-doo MX Z TNT 600 E-TEC direct injected two stroke, Polaris 800 Rush semi-direct injected two-stroke, and an Arctic Cat F570 carbureted two-stroke. All of the snowmobiles operate on open loop systems which means there was no compensation for the change in fuel properties. Emissions were sampled using a Sensors Inc. Semtech DS five gas emissions analyzer and engine data was recoded using AIM Racing Data Power EVO3 Pro and EVO4 systems. The recorded raw exhaust emissions included carbon monoxide (CO), carbon dioxide (CO2), total hydrocarbons (THC), and oxygen (O2). To help explain the trends in the emissions data, engine parameters were also recorded. The EVO equipment was installed on each vehicle to record the following parameters: engine speed, exhaust gas temperature, head temperature, coolant temperature, and test cell air temperature. At least three consistent tests to ensure repeatability were taken at each fuel and temperature combination so a total of 18 valid tests were taken on each snowmobile. The snowmobiles were run at operating temperature to clear any excess fuel in the engine crankcase before each cold-start test. The trends from switching from E0 to E15 were different for each snowmobile as they all employ different engine technologies. The Yamaha snowmobile (four-stroke EFI) achieved higher levels of CO2 with lower CO and THC emissions on E15. Engine speeds were fairly consistent between fuels but the average engine speeds were increased as the temperatures decreased. The average exhaust gas temperature increased from 1.3-1.8% for the E15 compared to E0 due to enleanment. For the Ski-doo snowmobile (direct injected two-stroke) only slight differences were noted when switching from E0 to E15. This could possibly be due to the lean of stoichiometric operation of the engine at idle. The CO2 emissions decreased slightly at 20 °F and 0 °F for E15 fuel with a small difference at -20 °F. Almost no change in CO or THC emissions was noted for all temperatures. The only significant difference in the engine data observed was the exhaust gas temperature which decreased with E15. The Polaris snowmobile (semi-direct injected two-stroke) had similar raw exhaust emissions for each of the two fuels. This was probably due to changing a resistor when using E15 which changed the fuel map for an ethanol mixture (E10 vs. E0). This snowmobile operates at a rich condition which caused the engine to emit higher values of CO than CO2 along with exceeding the THC analyzer range at idle. The engine parameters and emissions did not increase or decrease significantly with decreasing temperature. The average idle engine speed did increase as the ambient temperature decreased. The Arctic Cat snowmobile (carbureted two-stroke) was equipped with a choke lever to assist cold-starts. The choke was operated in the same manor for both fuels. Lower levels of CO emissions with E15 fuel were observed yet the THC emissions exceeded the analyzer range. The engine had a slightly lower speed with E15.