1 resultado para Delitos y faltas-Pleitos
em Universidade Federal do Rio Grande do Norte(UFRN)
Resumo:
The performance of algorithms for fault location i n transmission lines is directly related to the accuracy of its input data. Thus, fa ctors such as errors in the line parameters, failures in synchronization of oscillographic recor ds and errors in measurements of voltage and current can significantly influence the accurac y of algorithms that use bad data to indicate the fault location. This work presents a new method ology for fault location in transmission lines based on the theory of state estimation in or der to determine the location of faults more accurately by considering realistic systematic erro rs that may be present in measurements of voltage and current. The methodology was implemente d in two stages: pre-fault and post- fault. In the first step, assuming non-synchronized data, the synchronization angle and positive sequence line parameters are estimated, an d in the second, the fault distance is estimated. Besides calculating the most likely faul t distance obtained from measurement errors, the variance associated with the distance f ound is also determined, using the errors theory. This is one of the main contributions of th is work, since, with the proposed algorithm, it is possible to determine a most likely zone of f ault incidence, with approximately 95,45% of confidence. Tests for evaluation and validation of the proposed algorithm were realized from actual records of faults and from simulations of fictitious transmission systems using ATP software. The obtained results are relevant to show that the proposed estimation approach works even adopting realistic variances, c ompatible with real equipments errors.