12 resultados para Distribution network reconfiguration problem
em Universitat de Girona, Spain
Resumo:
Monitor a distribution network implies working with a huge amount of data coining from the different elements that interact in the network. This paper presents a visualization tool that simplifies the task of searching the database for useful information applicable to fault management or preventive maintenance of the network
Resumo:
This paper focus on the problem of locating single-phase faults in mixed distribution electric systems, with overhead lines and underground cables, using voltage and current measurements at the sending-end and sequence model of the network. Since calculating series impedance for underground cables is not as simple as in the case of overhead lines, the paper proposes a methodology to obtain an estimation of zero-sequence impedance of underground cables starting from previous single-faults occurred in the system, in which an electric arc occurred at the fault location. For this reason, the signal is previously pretreated to eliminate its peaks voltage and the analysis can be done working with a signal as close as a sinus wave as possible
Resumo:
The work presented in this paper belongs to the power quality knowledge area and deals with the voltage sags in power transmission and distribution systems. Propagating throughout the power network, voltage sags can cause plenty of problems for domestic and industrial loads that can financially cost a lot. To impose penalties to responsible party and to improve monitoring and mitigation strategies, sags must be located in the power network. With such a worthwhile objective, this paper comes up with a new method for associating a sag waveform with its origin in transmission and distribution networks. It solves this problem through developing hybrid methods which hire multiway principal component analysis (MPCA) as a dimension reduction tool. MPCA reexpresses sag waveforms in a new subspace just in a few scores. We train some well-known classifiers with these scores and exploit them for classification of future sags. The capabilities of the proposed method for dimension reduction and classification are examined using the real data gathered from three substations in Catalonia, Spain. The obtained classification rates certify the goodness and powerfulness of the developed hybrid methods as brand-new tools for sag classification
Resumo:
The statistical analysis of literary style is the part of stylometry that compares measurable characteristics in a text that are rarely controlled by the author, with those in other texts. When the goal is to settle authorship questions, these characteristics should relate to the author’s style and not to the genre, epoch or editor, and they should be such that their variation between authors is larger than the variation within comparable texts from the same author. For an overview of the literature on stylometry and some of the techniques involved, see for example Mosteller and Wallace (1964, 82), Herdan (1964), Morton (1978), Holmes (1985), Oakes (1998) or Lebart, Salem and Berry (1998). Tirant lo Blanc, a chivalry book, is the main work in catalan literature and it was hailed to be “the best book of its kind in the world” by Cervantes in Don Quixote. Considered by writters like Vargas Llosa or Damaso Alonso to be the first modern novel in Europe, it has been translated several times into Spanish, Italian and French, with modern English translations by Rosenthal (1996) and La Fontaine (1993). The main body of this book was written between 1460 and 1465, but it was not printed until 1490. There is an intense and long lasting debate around its authorship sprouting from its first edition, where its introduction states that the whole book is the work of Martorell (1413?-1468), while at the end it is stated that the last one fourth of the book is by Galba (?-1490), after the death of Martorell. Some of the authors that support the theory of single authorship are Riquer (1990), Chiner (1993) and Badia (1993), while some of those supporting the double authorship are Riquer (1947), Coromines (1956) and Ferrando (1995). For an overview of this debate, see Riquer (1990). Neither of the two candidate authors left any text comparable to the one under study, and therefore discriminant analysis can not be used to help classify chapters by author. By using sample texts encompassing about ten percent of the book, and looking at word length and at the use of 44 conjunctions, prepositions and articles, Ginebra and Cabos (1998) detect heterogeneities that might indicate the existence of two authors. By analyzing the diversity of the vocabulary, Riba and Ginebra (2000) estimates that stylistic boundary to be near chapter 383. Following the lead of the extensive literature, this paper looks into word length, the use of the most frequent words and into the use of vowels in each chapter of the book. Given that the features selected are categorical, that leads to three contingency tables of ordered rows and therefore to three sequences of multinomial observations. Section 2 explores these sequences graphically, observing a clear shift in their distribution. Section 3 describes the problem of the estimation of a suden change-point in those sequences, in the following sections we propose various ways to estimate change-points in multinomial sequences; the method in section 4 involves fitting models for polytomous data, the one in Section 5 fits gamma models onto the sequence of Chi-square distances between each row profiles and the average profile, the one in Section 6 fits models onto the sequence of values taken by the first component of the correspondence analysis as well as onto sequences of other summary measures like the average word length. In Section 7 we fit models onto the marginal binomial sequences to identify the features that distinguish the chapters before and after that boundary. Most methods rely heavily on the use of generalized linear models
Resumo:
This paper presents a new charging scheme for cost distribution along a point-to-multipoint connection when destination nodes are responsible for the cost. The scheme focus on QoS considerations and a complete range of choices is presented. These choices go from a safe scheme for the network operator to a fair scheme to the customer. The in-between cases are also covered. Specific and general problems, like the incidence of users disconnecting dynamically is also discussed. The aim of this scheme is to encourage the users to disperse the resource demand instead of having a large number of direct connections to the source of the data, which would result in a higher than necessary bandwidth use from the source. This would benefit the overall performance of the network. The implementation of this task must balance between the necessity to offer a competitive service and the risk of not recovering such service cost for the network operator. Throughout this paper reference to multicast charging is made without making any reference to any specific category of service. The proposed scheme is also evaluated with the criteria set proposed in the European ATM charging project CANCAN
Resumo:
The authors focus on one of the methods for connection acceptance control (CAC) in an ATM network: the convolution approach. With the aim of reducing the cost in terms of calculation and storage requirements, they propose the use of the multinomial distribution function. This permits direct computation of the associated probabilities of the instantaneous bandwidth requirements. This in turn makes possible a simple deconvolution process. Moreover, under certain conditions additional improvements may be achieved
Resumo:
Fault location has been studied deeply for transmission lines due to its importance in power systems. Nowadays the problem of fault location on distribution systems is receiving special attention mainly because of the power quality regulations. In this context, this paper presents an application software developed in Matlabtrade that automatically calculates the location of a fault in a distribution power system, starting from voltages and currents measured at the line terminal and the model of the distribution power system data. The application is based on a N-ary tree structure, which is suitable to be used in this application due to the highly branched and the non- homogeneity nature of the distribution systems, and has been developed for single-phase, two-phase, two-phase-to-ground, and three-phase faults. The implemented application is tested by using fault data in a real electrical distribution power system
Resumo:
This paper shows how instructors can use the problem‐based learning method to introduce producer theory and market structure in intermediate microeconomics courses. The paper proposes a framework where different decision problems are presented to students, who are asked to imagine that they are the managers of a firm who need to solve a problem in a particular business setting. In this setting, the instructors’ role is to provide both guidance to facilitate student learning and content knowledge on a just‐in‐time basis
Resumo:
Els sistemes aquàtics continental representen un dels ecosistemes més amenaçats a nivell mundial, com a conseqüència de l'ús intensiu quel'home en fa. La conca del Guadiana no està lliure d'aquestes pressions antròpiques. Les grans infraestructures hidràuliques i l'escorrentia provinent de l'agricultura són només exemples dels greus problemes que pateix la conca. Aquests problemes es fan especialment palesos en la zona alta de la conca, on l'escassetat d'aigua no fa més que agreujar el problema.Tot això ha generat la necessitat urgent d'avaluar l'estat de conservació d'aquests ecosistemes aquàtics continentals, poder determinar la mesura i la magnitud de les pertorbacions que els estan afectant i així proposar mesures de gestió destinades a restaurar-ne la integritat ecològica. El principal objectiu que presenta aquest és determinar els patrons de distribució de les comunitats de algals (amb una menció especial en el grup de les diatomees) i de les seves causes en la conca del Guadiana i associades, amb la finalitat d'establir i proposar eines que permetin avaluar l'estat de conservació de les masses d'aigua d'aquestes conques.
Resumo:
This thesis proposes a framework for identifying the root-cause of a voltage disturbance, as well as, its source location (upstream/downstream) from the monitoring place. The framework works with three-phase voltage and current waveforms collected in radial distribution networks without distributed generation. Real-world and synthetic waveforms are used to test it. The framework involves features that are conceived based on electrical principles, and assuming some hypothesis on the analyzed phenomena. Features considered are based on waveforms and timestamp information. Multivariate analysis of variance and rule induction algorithms are applied to assess the amount of meaningful information explained by each feature, according to the root-cause of the disturbance and its source location. The obtained classification rates show that the proposed framework could be used for automatic diagnosis of voltage disturbances collected in radial distribution networks. Furthermore, the diagnostic results can be subsequently used for supporting power network operation, maintenance and planning.
Resumo:
This dissertation focuses on the problem of providing mechanisms for routing point to point and multipoint connections in ATM networks. In general the notion of multipoint connection refers to connections that involve a group of users with more than two members. The main objective of this dissertation is to contribute to design efficient routing protocols with alterative routes in fully connected VP-based ATM Networks for call establishment of point to point and multipoint VC connections. An efficient route should be computed during this connection establishment phase.
Resumo:
La calidad de energía eléctrica incluye la calidad del suministro y la calidad de la atención al cliente. La calidad del suministro a su vez se considera que la conforman dos partes, la forma de onda y la continuidad. En esta tesis se aborda la continuidad del suministro a través de la localización de faltas. Este problema se encuentra relativamente resuelto en los sistemas de transmisión, donde por las características homogéneas de la línea, la medición en ambos terminales y la disponibilidad de diversos equipos, se puede localizar el sitio de falta con una precisión relativamente alta. En sistemas de distribución, sin embargo, la localización de faltas es un problema complejo y aún no resuelto. La complejidad es debida principalmente a la presencia de conductores no homogéneos, cargas intermedias, derivaciones laterales y desbalances en el sistema y la carga. Además, normalmente, en estos sistemas sólo se cuenta con medidas en la subestación, y un modelo simplificado del circuito. Los principales esfuerzos en la localización han estado orientados al desarrollo de métodos que utilicen el fundamental de la tensión y de la corriente en la subestación, para estimar la reactancia hasta la falta. Como la obtención de la reactancia permite cuantificar la distancia al sitio de falta a partir del uso del modelo, el Método se considera Basado en el Modelo (MBM). Sin embargo, algunas de sus desventajas están asociadas a la necesidad de un buen modelo del sistema y a la posibilidad de localizar varios sitios donde puede haber ocurrido la falta, esto es, se puede presentar múltiple estimación del sitio de falta. Como aporte, en esta tesis se presenta un análisis y prueba comparativa entre varios de los MBM frecuentemente referenciados. Adicionalmente se complementa la solución con métodos que utilizan otro tipo de información, como la obtenida de las bases históricas de faltas con registros de tensión y corriente medidos en la subestación (no se limita solamente al fundamental). Como herramienta de extracción de información de estos registros, se utilizan y prueban dos técnicas de clasificación (LAMDA y SVM). Éstas relacionan las características obtenidas de la señal, con la zona bajo falta y se denominan en este documento como Métodos de Clasificación Basados en el Conocimiento (MCBC). La información que usan los MCBC se obtiene de los registros de tensión y de corriente medidos en la subestación de distribución, antes, durante y después de la falta. Los registros se procesan para obtener los siguientes descriptores: a) la magnitud de la variación de tensión ( dV ), b) la variación de la magnitud de corriente ( dI ), c) la variación de la potencia ( dS ), d) la reactancia de falta ( Xf ), e) la frecuencia del transitorio ( f ), y f) el valor propio máximo de la matriz de correlación de corrientes (Sv), cada uno de los cuales ha sido seleccionado por facilitar la localización de la falta. A partir de estos descriptores, se proponen diferentes conjuntos de entrenamiento y validación de los MCBC, y mediante una metodología que muestra la posibilidad de hallar relaciones entre estos conjuntos y las zonas en las cuales se presenta la falta, se seleccionan los de mejor comportamiento. Los resultados de aplicación, demuestran que con la combinación de los MCBC con los MBM, se puede reducir el problema de la múltiple estimación del sitio de falta. El MCBC determina la zona de falta, mientras que el MBM encuentra la distancia desde el punto de medida hasta la falta, la integración en un esquema híbrido toma las mejores características de cada método. En este documento, lo que se conoce como híbrido es la combinación de los MBM y los MCBC, de una forma complementaria. Finalmente y para comprobar los aportes de esta tesis, se propone y prueba un esquema de integración híbrida para localización de faltas en dos sistemas de distribución diferentes. Tanto los métodos que usan los parámetros del sistema y se fundamentan en la estimación de la impedancia (MBM), como aquellos que usan como información los descriptores y se fundamentan en técnicas de clasificación (MCBC), muestran su validez para resolver el problema de localización de faltas. Ambas metodologías propuestas tienen ventajas y desventajas, pero según la teoría de integración de métodos presentada, se alcanza una alta complementariedad, que permite la formulación de híbridos que mejoran los resultados, reduciendo o evitando el problema de la múltiple estimación de la falta.