3 resultados para CURRENT DISTRIBUTION
em Universitat de Girona, Spain
Resumo:
This paper focus on the problem of locating single-phase faults in mixed distribution electric systems, with overhead lines and underground cables, using voltage and current measurements at the sending-end and sequence model of the network. Since calculating series impedance for underground cables is not as simple as in the case of overhead lines, the paper proposes a methodology to obtain an estimation of zero-sequence impedance of underground cables starting from previous single-faults occurred in the system, in which an electric arc occurred at the fault location. For this reason, the signal is previously pretreated to eliminate its peaks voltage and the analysis can be done working with a signal as close as a sinus wave as possible
Resumo:
Les algues del gènere Cystoseira són els principals organismes formadors d'estructura en fons rocosos ben il·luminats del Mar Mediterrani. Formen unes comunitats molt estructurades que s'assemblen ecològicament als boscos terrestres i que són sensibles als impactes antròpics. Aquesta tesi s'ha centrat en l'estudi de les espècies i comunitats dominades per Cystoseira que es troben en ambients calmats, és a dir, en petites cales i/o badies. S'han abordat diversos aspectes com són la distribució, composició, estructura i biogeografia d'aquestes comunitats, així com els efectes de la contaminació sobre les mateixes. Per una banda, s'ha documentat l'estat actual de les comunitats dominades per C. crinita a nombrosos llocs al llarg de tot el Mediterrani, aportant informació sobre la seva composició, estructura, variació biogeogràfica i dinàmica de la comunitat a llarg termini. S'ha documentat la desaparició de diverses espècies de Cystoseira en zones afectades per impactes antròpics diversos i s'ha proporcionat la primera evidència experimental de la desaparició d'espècies de Cystoseira a causa de la contaminació.
Resumo:
This thesis proposes a framework for identifying the root-cause of a voltage disturbance, as well as, its source location (upstream/downstream) from the monitoring place. The framework works with three-phase voltage and current waveforms collected in radial distribution networks without distributed generation. Real-world and synthetic waveforms are used to test it. The framework involves features that are conceived based on electrical principles, and assuming some hypothesis on the analyzed phenomena. Features considered are based on waveforms and timestamp information. Multivariate analysis of variance and rule induction algorithms are applied to assess the amount of meaningful information explained by each feature, according to the root-cause of the disturbance and its source location. The obtained classification rates show that the proposed framework could be used for automatic diagnosis of voltage disturbances collected in radial distribution networks. Furthermore, the diagnostic results can be subsequently used for supporting power network operation, maintenance and planning.