64 resultados para waste handling


Relevância:

20.00% 20.00%

Publicador:

Resumo:

Biodegradable waste quantities in Lithuania and their potential for the co-treatment in renewable energy and organic fertilizer production are investigated. Two scenarios are formulated to study the differences of the amounts of obtainable energy and fertilizers between different ways of utilization. In the first scenario, only digestion is used, and in the second scenario, other materials than straw are digested, and straw and the solid fraction of sewage sludge digestate are combusted. As a result, the amounts of heat and electricity, as well as the fertilizer amounts in the counties are obtained for both scenarios. Based on this study, the share of renewable energy in Lithuania could be doubled by the co-treatment of different biodegradable materials.

Relevância:

20.00% 20.00%

Publicador:

Resumo:

Fluid handling systems account for a significant share of the global consumption of electrical energy. They also suffer from problems, which reduce their energy efficiency and increase life-cycle costs. Detecting or predicting these problems in time can make fluid handling systems more environmentally and economically sustainable to operate. In this Master’s Thesis, significant problems in fluid systems were studied and possibilities to develop variable-speed-drive-based detection methods for them was discussed. A literature review was conducted to find significant problems occurring in fluid handling systems containing pumps, fans and compressors. To find case examples for evaluating the feasibility of variable-speed-drive-based methods, queries were sent to industrial companies. As a result of this, the possibility to detect heat exchanger fouling with a variable-speed drive was analysed with data from three industrial cases. It was found that a mass flow rate estimate, which can be generated with a variable speed drive, can be used together with temperature measurements to monitor a heat exchanger’s thermal performance. Secondly, it was found that the fouling-related increase in the pressure drop of a heat exchanger can be monitored with a variable speed drive. Lastly, for systems where the flow device is speed controlled with by a pressure measurement, it was concluded that increasing rotational speed can be interpreted as progressing fouling in the heat exchanger.