43 resultados para Automatic voltage regulator. Sliding surface. Salient pole synchronous generator. Power system stabilizer
em QUB Research Portal - Research Directory and Institutional Repository for Queen's University Belfast
Resumo:
Synchronisation of small distributed generation, 30 kVA–2 MVA, employing salient-pole synchronous machines is normally performed within a narrow range of tolerances for voltage, frequency and phase angle. However, there are situations when the ability to synchronise with non-ideal conditions would be beneficial. Such applications include power system islanding and rapid generator start-up. The physical process and effect of out-of-phase synchronisation is investigated both through simulation and experimental tests on a salient-pole alternator. There are many factors that affect synchronisation, but particular attention is given to synchronisation angle, voltage difference and, as generators will be loaded during islanding, the load angle. The results suggest that it would be acceptable for the maximum synchronisation angle of distributed generation to exceed that of current practice. Interesting observations on the nature of out-of-phase synchronisation are made, including some specific to small salient-pole synchronous machines. Furthermore, recommendations are made for synchronisation under different system conditions.
Resumo:
Small salient-pole machines, in the range 30 kVA to 2 MVA, are often used in distributed generators, which in turn are likely to form the major constituent of power generation in power system islanding schemes or microgrids. In addition to power system faults, such as short-circuits, islanding contains an inherent risk of out-of-synchronism re-closure onto the main power system. To understand more fully the effect of these phenomena on a small salient-pole alternator, the armature and field currents from tests conducted on a 31.5 kVA machine are analysed. This study demonstrates that by resolving the voltage difference between the machine terminals and bus into direct and quadrature axis components, interesting properties of the transient currents are revealed. The presence of saliency and short time-constants cause intriguing differences between machine events such as out-of-phase synchronisations and sudden three-phase short-circuits.
Resumo:
Damping torque analysis is a well-developed technique for understanding and studying power system oscillations. This paper presents the applications of damping torque analysis for DC bus implemented damping control in power transmission networks in two examples. The first example is the investigation of damping effect of shunt VSC (Voltage Source Converter) based FACTS voltage control, i.e., STATCOM (Static Synchronous Compensator) voltage control. It is shown in the paper that STATCOM voltage control mainly contributes synchronous torque and hence has little effect on the damping of power system oscillations. The second example is the damping control implemented by a Battery Energy Storage System (BESS) installed in a power system. Damping torque analysis reveals that when BESS damping control is realized by regulating exchange of active and reactive power between the BESS and power system respectively, BESS damping control exhibits different properties. It is concluded by damping torque analysis that BESS damping control implemented by regulating active power is better with less interaction with BESS voltage control and more robust to variations of power system operating conditions. In the paper, all analytical conclusions obtained are demonstrated by simulation results of example power systems.
Resumo:
An analysis of a modified series-L/parallel-tuned Class-E power amplifier is presented, which includes the effects that a shunt capacitance placed across the switching device will have on Class-E behaviour. In the original series L/parallel-tuned topology in which the output transistor capacitance is not inherently included in the circuit, zero-current switching (ZCS) and zero-current derivative switching (ZCDS) conditions should be applied to obtain optimum Class-E operation. On the other hand, when the output transistor capacitance is incorporated in the circuit, i.e. in the modified series-L/parallel-tuned topology, the ZCS and ZCDS would not give optimum operation and therefore zero-voltage-switching (ZVS) and zero-voltage-derivative switching (ZVDS) conditions should be applied instead. In the modified series-L/parallel-tuned Class-E configuration, the output-device inductance and the output-device output capacitance, both of which can significantly affect the amplifier's performance at microwave frequencies, furnish part, if not all, of the series inductance L and the shunt capacitance COUT, respectively. Further, when compared with the classic shunt-C/series-tuned topology, the proposed Class-E configuration offers some advantages in terms of 44% higher maximum operating frequency (fMAX) and 4% higher power-output capability (PMAX). As in the classic topology, the fMAX of the proposed amplifier circuit is reached when the output-device output capacitance furnishes all of the capacitance COUT, for a given combination of frequency, output power and DC supply voltage. It is also shown that numerical simulations agree well with theoretical predictions.
Resumo:
This paper discusses the use of primary frequency response metrics to assess the dynamics of frequency disturbance data with the presence of high system non synchronous penetration (SNSP) and system inertia variation. The Irish power system has been chosen as a study case as it experiences a significant level of SNSP from wind turbine generation and imported active power from HVDC interconnectors. Several recorded actual frequency disturbances were used in the analysis. These data were measured and collected from the Irish power system from October 2010 to June 2013. The paper has shown the impact of system inertia and SNSP variation on the performance of primary frequency response metrics, namely: nadir frequency, rate of change of frequency, inertial and primary frequency response.
Resumo:
The small signal stability of interconnected power systems is one of the important aspects that need to be investigated since the oscillations caused by this kind of instability have caused many incidents. With the increasing penetration of wind power in the power system, particularly doubly fed induction generator (DFIG), the impact on the power system small signal stability performance should be fully investigated. Because the DFIG wind turbine integration is through a fast action converter and associated control, it does not inherently participate in the electromechanical small signal oscillation. However, it influences the small signal stability by impacting active power flow paths in the network and replacing synchronous generators that have power system stabilizer (PSS). In this paper, the IEEE 39 bus test system has been used in the analysis. Furthermore, four study cases and several operation scenarios have been conducted and analysed. The selective eigenvalue Arnoldi/lanczos's method is used to obtain the system eigenvalue in the range of frequency from 0.2 Hz to 2 Hz which is related to electromechanical oscillations. Results show that the integration of DFIG wind turbines in a system during several study cases and operation scenarios give different influence on small signal stability performance.
Resumo:
A new linear indicator is presented together with a comparative study with other published works. The salient advantage of the linear characteristic is emphasised. The new index is tested utilising the IEEE 30 bus test power system
Resumo:
This paper presents the results of feasibility study of a novel concept of power system on-line collaborative voltage stability control. The proposal of the on-line collaboration between power system controllers is to enhance their overall performance and efficiency to cope with the increasing operational uncertainty of modern power systems. In the paper, the framework of proposed on-line collaborative voltage stability control is firstly presented, which is based on the deployment of multi-agent systems and real-time communication for on-line collaborative control. Then two of the most important issues in implementing the proposed on-line collaborative voltage stability control are addressed: (1) Error-tolerant communication protocol for fast information exchange among multiple intelligent agents; (2) Deployment of multi-agent systems by using graph theory to implement power system post-emergency control. In the paper, the proposed on-line collaborative voltage stability control is tested in the example 10-machine 39-node New England power system. Results of feasibility study from simulation are given considering the low-probability power system cascading faults.
Resumo:
This paper deals with Takagi-Sugeno (TS) fuzzy model identification of nonlinear systems using fuzzy clustering. In particular, an extended fuzzy Gustafson-Kessel (EGK) clustering algorithm, using robust competitive agglomeration (RCA), is developed for automatically constructing a TS fuzzy model from system input-output data. The EGK algorithm can automatically determine the 'optimal' number of clusters from the training data set. It is shown that the EGK approach is relatively insensitive to initialization and is less susceptible to local minima, a benefit derived from its agglomerate property. This issue is often overlooked in the current literature on nonlinear identification using conventional fuzzy clustering. Furthermore, the robust statistical concepts underlying the EGK algorithm help to alleviate the difficulty of cluster identification in the construction of a TS fuzzy model from noisy training data. A new hybrid identification strategy is then formulated, which combines the EGK algorithm with a locally weighted, least-squares method for the estimation of local sub-model parameters. The efficacy of this new approach is demonstrated through function approximation examples and also by application to the identification of an automatic voltage regulation (AVR) loop for a simulated 3 kVA laboratory micro-machine system.