88 resultados para Solar cooling system

em Queensland University of Technology - ePrints Archive


Relevância:

100.00% 100.00%

Publicador:

Resumo:

This thesis investigates the coefficient of performance (COP) of a hybrid liquid desiccant solar cooling system. This hybrid cooling system includes three sections: 1) conventional air-conditioning section; 2) liquid desiccant dehumidification section and 3) air mixture section. The air handling unit (AHU) with mixture variable air volume design is included in the hybrid cooling system to control humidity. In the combined system, the air is first dehumidified in the dehumidifier and then mixed with ambient air by AHU before entering the evaporator. Experiments using lithium chloride as the liquid desiccant have been carried out for the performance evaluation of the dehumidifier and regenerator. Based on the air mixture (AHU) design, the electrical coefficient of performance (ECOP), thermal coefficient of performance (TCOP) and whole system coefficient of performance (COPsys) models used in the hybrid liquid desiccant solar cooing system were developed to evaluate this system performance. These mathematical models can be used to describe the coefficient of performance trend under different ambient conditions, while also providing a convenient comparison with conventional air conditioning systems. These models provide good explanations about the relationship between the performance predictions of models and ambient air parameters. The simulation results have revealed the coefficient of performance in hybrid liquid desiccant solar cooling systems substantially depends on ambient air and dehumidifier parameters. Also, the liquid desiccant experiments prove that the latent component of the total cooling load requirements can be easily fulfilled by using the liquid desiccant dehumidifier. While cooling requirements can be met, the liquid desiccant system is however still subject to the hysteresis problems.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Solar cooling systems are gaining popularity due to continuously increasing of energy costs around the world. However, there are still some factors that are hindering the installation of solar cooling systems on a larger scale. One being the cost associated with the solar collectors required to provide heat to the absorption chiller. This study demonstrates the possibility of reducing the number of solar panels in a residential solar cooling system based on evacuated tubes producing hot water at a low temperature (90 °C) and a water-ammonia absorption chiller.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

Nowadays Solar Cooling systems are becoming popular to reduce the carbon footprint of air conditioning. The use of an absorption chiller connected to solar thermal panels is increasing, but little study has been carried out to assess the advantage of join together an absorption chiller and a desiccant wheel to remove the sensible heat and the latent heat in different ways than the current design adopted in the industry. In this work I assess the possibility of implement a desiccant wheel in a conventional solar cooling system and the possibility of recovering the heat rejected by the absorption chiller which is then used for the regeneration of the desiccant wheel. The implementation of a desiccant wheel and the recovery of the heat rejected could provide a significant energy saving when compared to traditional solar cooling system. The results assist in the practical development of a solar cooling system which simultaneously uses absorption and adsorption technology.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This paper investigates a pilot desalination system which consists of a direct expansion solar assisted heat pump (DXSAHP) coupled to a single-effect evaporator unit. The working fluid used is R134a and distillate is obtained via falling film evaporation and flashing in the unit. Experiments have been conducted in both day and night meteorological conditions in Singapore and the effects of solar irradiation and compressor speed have been studied against the system performance. From the experiments, the Performance Ratio (PR) obtained ranges from 0.43 to 0.88, the average Coefficient of Performance (COP) was 8 and the highest distillate production recorded was 1.38 kg/h

Relevância:

100.00% 100.00%

Publicador:

Resumo:

The drying of fruit and vegetables is a subject of great importance. Dried fruit and vegetables have gained commercial importance, and their growth on a commercial scale has become an important sector of the agricultural industry. However, food drying is one of the most energy intensive processes of the major industrial process and accounts for up to 15 % of all industrial energy usage. Due to increasingly high electricity prices and environmental concern, a dryer using traditional energy sources is not a feasible option anymore. Therefore, an alternative/renewable energy source is needed. In this regard, an integrated solar drying system that includes highly efficient double-pass counter flow v-groove solar collector, conical-shaped rock-bed thermal storage, auxiliary heater, the centrifugal fan and the drying chamber has been designed and constructed. Mathematical model for all the individual components as well as an integrated model combining all components of the drying system has been developed. Mathematical equations were solved using MATLAB program. This paper presents the analytical model and key finding of the simulation.

Relevância:

100.00% 100.00%

Publicador:

Resumo:

This study demonstrates the possibility of using an absorption chiller to produce chilled water for air conditioning, and at the same time recover the rejected heat producing domestic hot water. The absorption chiller considered for this application has been sized to suit a standard household and uses a solution of ammonia and water running on hot water at a temperature ranging from 80 - 120°C produced by thermal solar panels. The system consists of five main components: generator, rectifier, condenser, evaporator and absorber, and is divided in two sections at two different pressures. The section at higher pressure includes the generator, rectifier and condenser whereas the section at lower pressure includes the evaporator and the absorber. Heat in this type of system is usually rejected to the environment from the condenser, rectifier and absorber through a cooling tower or air cooler exchanger. In this paper we describe how to recover this heat to create domestic hot water by providing a quantitative evaluation of the amount of energy recovered by the proposed system, if used in the Australian region.

Relevância:

90.00% 90.00%

Publicador:

Resumo:

This research was commissioned by Metecno Pty Ltd, trading as Bondor®. The InsulLiving house was designed and constructed by Bondor®. The house instrumentation (electricity circuits, indoor environment, weather station) was provided by Bondor and supplied and installed by independent contractors. This report contains analysis of data collected from the InsulLiving house at Burpengary during 1 year of occupancy by a family of four for the period 1 April 2012 – 31 March 2013. The data shows a daily average electricity consumption 48% less than the regional average. The analysis confirms that the 9 star house performed thermally slightly better than the simulated performance. The home was 'near zero energy', with its modest 2.1kW solar power system meeting all of the needs for space heating and cooling, lighting and most water heating.

Relevância:

90.00% 90.00%

Publicador:

Resumo:

Taking into consideration of growing energy needs and concern for environmental degradation, clean and inexhaustible energy source, such as solar energy, is receiving greater attention for various applications. The use of solar energy system reduces pollution, waste and has little or no harmful effects on the environment. It is appreciated that this source of energy can be complementary rather than being competitive to conventional energy sources. In order to collect and harness energy from the sun, a solar collector is essential. A solar collector is basically a heat exchanger that transforms solar radiant energy into heat or thermal energy. Improvement of performance is essential for commercial acceptance of their use in such applications. Many studies have been undertaken on the enhancement of thermal performance of solar collectors, using diverse materials of various shapes, dimensions and layouts. In the literature, various collector designs have been proposed and tested with the objective of meeting these requirements [1-8]. Omer et al. [1] found the efficiency of a solar collector of about 70% in a solar assisted heat pump system. Traditional solar collectors are single phase collectors, in which the working fluid is either air or water. Different modifications are suggested and applied to improve the heat transfer between the absorber and working fluid in a collector. These modifications include the use of absorber with fins attached [2,3], corrugated absorber [4,5], matrix type absorber [6], V-groove solar air collector [7]. Karim et al. [8] approached a review of design and construction of three types (flat, vee-grooved, and finned) of air collectors. Two-phase collectors, on the other hand, have significant potential for continuous operation round the clock, when used in conjunction with a compressor, as found in a solar assisted heat-pump cycle.

Relevância:

90.00% 90.00%

Publicador:

Resumo:

Biofuel produced by fast pyrolysis from biomass is a promising candidate. The heart of the system is a reactor which is directly or indirectly heated to approximately 500°C by exhaust gases from a combustor that burns pyrolysis gas and some of the by-product char. In most of the cases, external biomass heater is used as heating source of the system while internal electrical heating is recently implemented as source of reactor heating. However, this heating system causes biomass or other conventional forms of fuel consumption to produce renewable energy and contributes to environmental pollution. In order to overcome these, the feasibility of incorporating solar energy with fast pyrolysis has been investigated. The main advantages of solar reactor heating include renewable source of energy, comparatively simpler devices, and no environmental pollution. A lab scale pyrolysis setup has been examined along with 1.2 m diameter parabolic reflector concentrator that provides hot exhaust gas up to 162°C. The study shows that about 32.4% carbon dioxide (CO2) emissions and almost one-third portion of fuel cost are reduced by incorporating solar heating system. Successful implementation of this proposed solar assisted pyrolysis would open a prospective window of renewable energy.

Relevância:

90.00% 90.00%

Publicador:

Resumo:

Melbourne-based manufacturer Muller Industries Australia’s new cooling system saves 80 per cent of the average water usage in commercial office buildings that use water-based cooling towers.

Relevância:

90.00% 90.00%

Publicador:

Resumo:

According to some embodiments, the present invention provides a novel photovoltaic solar cell system from photovoltaic modules that are vertically arrayed in a stack format using thin film semiconductors selected from among org. and inorg. thin film semiconductors. The stack cells may be cells that are produced in a planar manner, then vertically oriented in an angular form, also termed herein tilted, to maximize the light capturing aspects. The use of a stack configuration system as described herein allows for the use of a variety of electrode materials, such as transparent materials or semitransparent metals. Light concn. can be achieved by using fresnel lens, parabolic mirrors or derivs. of such structures. The light capturing can be controlled by being reflected back and forth in the photovoltaic system until significant quantities of the resonant light is absorbed. Light that passes to the end and can be reflected back through the device by beveling or capping the end of the device with a different refractive index material, or alternatively using a reflective surface. The contacting between stacked cells can be done in series or parallel. According to some embodiments, the present invention uses a concentrator architecture where the light is channeled into the cells that contain thermal fluid channels (using a transparent fluid such as water) to absorb and hence reduce the thermal energy generation.

Relevância:

50.00% 50.00%

Publicador:

Resumo:

This paper evaluates and compares the system performance of a solar desiccant-evaporative cooling (SDEC) system with a referenced conventional variable air volume (VAV) system for a typical office building in all 8 Australian capital cities. A simulation model of the building is developed using the whole building simulation software EnergyPlus. The performance indicators for the comparison are system coefficient of performance (COP), annual primary energy consumption, annual energy savings, and annual CO2 emissions reduction. The simulation results show that Darwin has the most apparent advantages for SDEC system applications with an annual energy savings of 557 GJ and CO2 emission reduction of 121 tonnes. The maximum system COP is 7. For other climate zones such as Canberra, Hobart and Melbourne, the SDEC system is not as energy efficient as the conventional VAV system.