1 resultado para Environmental Protection Agency, Washington, D.C.

em Indian Institute of Science - Bangalore - Índia


Relevância:

100.00% 100.00%

Publicador:

Resumo:

Bypass operation with the aid of a special bypass valve is an important part of present-day schemes of protection for h.v. d.c. transmission systems. In this paper, the possibility of using two valves connected to any phase in the bridge convertor for the purpose of bypass operation is studied. The scheme is based on the use of logic circuits in conjunction with modified methods of fault detection. Analysis of the faults in a d.c. transmission system is carried out with the object of determining the requirements of such a logic-circuit control system. An outline of the scheme for the logic-circuit control of the bypass operation for both rectifier and invertor bridges is then given. Finally, conclusions are drawn regarding the advantages of such a system, which include reduction in the number of valves, prevention of severe faults and fast clearance of faults, in addition to the immediate location of the fault and its nature.