143 resultados para Electric machines
em Indian Institute of Science - Bangalore - Índia
Resumo:
This paper reports the dynamic stability analysis of a single machine infinite bus system through torque angle loop analysis and forms an extension of the work on Block diagrams and torque angle loop analysis of synchronous machines reported by I. Nagy [3]. It aims to incorporate in the machine model, the damper windings (one on each axis) and to compare the dynamic behaviour of the system with and without damper windings. The effect of using different stabilizing signals (viz. active power and speed deviations) on the dynamic performance is analysed and the significant effect of damper windings on the dynamic behaviour of the system is highlighted.
Resumo:
This paper presents three methodologies for determining optimum locations and magnitudes of reactive power compensation in power distribution systems. Method I and Method II are suitable for complex distribution systems with a combination of both radial and ring-main feeders and having different voltage levels. Method III is suitable for low-tension single voltage level radial feeders. Method I is based on an iterative scheme with successive powerflow analyses, with formulation and solution of the optimization problem using linear programming. Method II and Method III are essentially based on the steady state performance of distribution systems. These methods are simple to implement and yield satisfactory results comparable with the results of Method I. The proposed methods have been applied to a few distribution systems, and results obtained for two typical systems are presented for illustration purposes.
Resumo:
The paper describes a Simultaneous Implicit (SI) approach for transient stability simulations based on an iterative technique using traingularised admittance matrix [1]. The reduced saliency of generator in the subtransient state is taken advantage of to speed up the algorithm. Accordingly, generator differential equations, except rotor swing, contain voltage proportional to fluxes in the main field, dampers and a hypothetical winding representing deep flowing eddy currents, as state variables. The simulation results are validated by comparison with two independent methods viz. Runge-Kutta simulation for a simplified system and a method based on modelling damper windings using conventional induction motor theory.
Resumo:
For systems which can be decomposed into slow and fast subsystems, a near optimum linear state regulator consisting of two subsystem regulators can be developed. Depending upon the desired criteria, either a short term (fast controller) or a long term controller (slow controller) can be easily designed with minimum computational costs. Using this approach an example of a power system supplying a cyclic load is studied and the performance of the different controllers are compared.
Resumo:
In the recent past it has been found that HVDC transmission systems and turbine-generator shaft torsional dynamics can interact in an unfavourable manner. This paper presents a detailed linearised state space model of AC/DC system to study this torsional interaction. The model developed is used to study the effect of various system parameters, such as, dc line loading, converter firing angle, the firing scheme employed. The results obtained are compared with those given in[3].
Resumo:
A novel method to account for the transmission line resistances in structure preserving energy functions (SPEF) is presented in this paper. The method exploits the equivalence of a lossy network having the same conductance to susceptance ratio for all its elements to a lossless network with a new set of power injections. The system equations and the energy function are developed using centre of inertia (COI) variables and the loads are modelled as arbitrary functions of respective bus voltages. The application of SPEF to direct transient stability evaluation is presented considering a realistic power system example.
Resumo:
Utilizing a circuit model [1, 2] of an induction motor, a simplified analysis of steady state performance of a voltage controlled induction motor (VCIM) drive is described in this paper. By solving a set of nonlinear algebraic equations which describe the VCIM drive under steady operation, the operating variables such as constant components of torque, rotor flux linkages, fundamental components of stator voltage and current and phase angle are obtained for any given value of slip, triggering angle and supply voltage.
Resumo:
This paper presents the detailed dynamic digital simulation for the study of phenomenon of torsional interaction between HVDC-Turbine generator shaft, dynamics using the novel converter model presented in [ 1 ] The system model includes detailed representation of the synchronous generator and the shaft dynamics, the ac and dc network transients. The results of a case study indicate the various factors that influence the torsional interaction.
Resumo:
This paper is concerned with the influence of different levels of complexity in modelling various constituent subsystems on the dynamic stability of power systems compensated by static var systems (SVS) operating on pure voltage control. The system components investigated include thyristor controlled reactor (TCR) transients, SVS delays, network transients, the synchronous generator and automatic voltage regulator (AVR). An overall model is proposed which adequately describes the system performance for small signal perturbations. The SVS performance is validated through detailed nonlinear simulation on a physical simulator.
Resumo:
Torsional interactions can occur due to the speed input Power System Stabilizer (PSS) that are primarily used to damp low frequency oscillations. The solution to this problem can be either in the form of providing a torsional filter or developing an alternate signal for the PSS. This paper deals with the formulation of a linearized state space model of the system and study of the interactions using eigenvalue analysis. The effects of the parameters of PSS and control signals on the damping of torsional modes are investigated.
Resumo:
This paper presents the design and development of a comprehensive digital protection scheme for applications in 25 KV a.c railway traction system. The scheme provides distance protection, detection of wrong phase coupling both in the lagging and leading directions, high set instantaneous trip and PT fuse failure. Provision is also made to include fault location and disturbance recording. The digital relaying scheme has been tried on two types of hardware platforms, one with PC/AT based hardware and the other with a custom designed standalone 16-bit microcontroller based card. Compared to the existing scheme, the operating time is around one cycle and the relaying algorithm has been optimised to minimise the number of computations. The prototype has been rigorously tested in the laboratory using a specially designed PC based relay test bench and the results are highly satisfactory.
Resumo:
The ability of Static Var Compensators (SVCs) to rapidly and continuously control reactive power in response to changing system conditions can result in the improvement of system stability and also increase the power transfer in the transmission system. This paper concerns the application of strategically located SVCs to enhance the transient stability limits and the direct evaluation of the effect of these SVCs on transient stability using a Structure Preserving Energy Function (SPEF). The SVC control system can be modelled from the steady- state control characteristic to accurately simulate its effect on transient stability. Treating the SVC as a voltage-dependent reactive power load leads to the derivation of a path-independent SPEF for the SVC. Case studies on a 10-machine test system using multiple SVCs illustrate the effects of SVCs on transient stability and its accurate prediction.
Resumo:
This paper presents a new approach to the power flow analysis in steady state for multiterminal DC-AC systems. A flexible and practical choice of per unit system is used to formulate the DC network and converter equations. A converter is represented by Norton's equivalent of a current source in parallel with the commutation resistance. Unlike in previous literature, the DC network equations are used to derive the controller equations for the DC system using a subset of specifications. The specifications considered are current or power at all terminals except the slack terminal where the DC voltage is specified. The control equations are solved by Newton's method, using the current injections at the converter terminals as state variables. Further, a systematic approach to the handling of constraints is proposed by identifying the priorities in rescheduling of the specified variables. The methodology is illustrated by example of a 5 terminal DC system.
Intelligent Approach for Fault Diagnosis in Power Transmission Systems Using Support Vector Machines
Resumo:
This paper presents an approach for identifying the faulted line section and fault location on transmission systems using support vector machines (SVMs) for diagnosis/post-fault analysis purpose. Power system disturbances are often caused by faults on transmission lines. When fault occurs on a transmission system, the protective relay detects the fault and initiates the tripping operation, which isolates the affected part from the rest of the power system. Based on the fault section identified, rapid and corrective restoration procedures can thus be taken to minimize the power interruption and limit the impact of outage on the system. The approach is particularly important for post-fault diagnosis of any mal-operation of relays following a disturbance in the neighboring line connected to the same substation. This may help in improving the fault monitoring/diagnosis process, thus assuring secure operation of the power systems. In this paper we compare SVMs with radial basis function neural networks (RBFNN) in data sets corresponding to different faults on a transmission system. Classification and regression accuracy is reported for both strategies. Studies on a practical 24-Bus equivalent EHV transmission system of the Indian Southern region is presented for indicating the improved generalization with the large margin classifiers in enhancing the efficacy of the chosen model.
Resumo:
This paper presents a multi-class support vector machine (SVMs) approach for locating and diagnosing faults in electric power distribution feeders with the penetration of Distributed Generations (DGs). The proposed approach is based on the three phase voltage and current measurements which are available at all the sources i.e. substation and at the connection points of DG. To illustrate the proposed methodology, a practical distribution feeder emanating from 132/11kV-grid substation in India with loads and suitable number of DGs at different locations is considered. To show the effectiveness of the proposed methodology, practical situations in distribution systems (DS) such as all types of faults with a wide range of varying fault locations, source short circuit (SSC) levels and fault impedances are considered for studies. The proposed fault location scheme is capable of accurately identify the fault type, location of faulted feeder section and the fault impedance. The results demonstrate the feasibility of applying the proposed method in practical in smart grid distribution automation (DA) for fault diagnosis.