On-line partial discharge (PD) measurements have become a common technique for assessing the insulation condition of installed high voltage (HV) insulated cables. When on-line tests are performed in noisy environments, or when more than one source of pulse-shaped signals are present in a cable system, it is difficult to perform accurate diagnoses. In these cases, an adequate selection of the non-conventional measuring technique and the implementation of effective signal processing tools are essential for a correct evaluation of the insulation degradation. Once a specific noise rejection filter is applied, many signals can be identified as potential PD pulses, therefore, a classification tool to discriminate the PD sources involved is required. This paper proposes an efficient method for the classification of PD signals and pulse-type noise interferences measured in power cables with HFCT sensors. By using a signal feature generation algorithm, representative parameters associated to the waveform of each pulse acquired are calculated so that they can be separated in different clusters. The efficiency of the clustering technique proposed is demonstrated through an example with three different PD sources and several pulse-shaped interferences measured simultaneously in a cable system with a high frequency current transformer (HFCT).

Relevância:

30.00% 30.00%

Publicador:

Resumo:

In this paper, a novel excitation-system ground-fault location method is described and tested in a 106 MVA synchronous machine. In this unit, numerous rotor ground-fault trips took place always about an hour after the synchronization to the network. However, when the field winding insulation was checked after the trips, there was no failure. The data indicated that the faults in the rotor were caused by centrifugal forces and temperature. Unexpectedly, by applying this new method, the failure was located in a cable between the excitation transformer and the automatic voltage regulator. In addition, several intentional ground faults were performed along the field winding with different fault resistance values, in order to test the accuracy of this method to locate defects in rotor windings of large generators. Therefore, this new on-line rotor ground-fault detection algorithm is tested in high-power synchronous generators with satisfactory results.