Optimum switching point assessment of parallel braking resistor and serial current limiter for power system stability enhancement


Autoria(s): Cao, G.; Dong, Z. Y.; Wang, Y.
Data(s)

01/01/2006

Resumo

A new control algorithm using parallel braking resistor (BR) and serial fault current limiter (FCL) for power system transient stability enhancement is presented in this paper. The proposed control algorithm can prevent transient instability during first swing by immediately taking away the transient energy gained in faulted period. It can also reduce generator oscillation time and efficiently make system back to the post-fault equilibrium. The algorithm is based on a new system energy function based method to choose optimal switching point. The parallel BR and serial FCL resistor can be switched at the calculated optimal point to get the best control result. This method allows optimum dissipation of the transient energy caused by disturbance so to make system back to equilibrium in minimum time. Case studies are given to verify the efficiency and effectiveness of this new control algorithm.

Identificador

http://espace.library.uq.edu.au/view/UQ:104384

Idioma(s)

eng

Publicador

The Institution of Engineering and Technology Hong Kong

Palavras-Chave #E1 #290901 Electrical Engineering #669900 Other
Tipo

Conference Paper