Eigenvalue sensitivity analysis for probabilistic small signal stability assessment


Autoria(s): Ma, Jian; Dong, Zhao Yang
Contribuinte(s)

K. K. Li

Data(s)

01/01/2006

Resumo

This paper presents a method to analyze the first order eigenvalue sensitivity with respect to the operating parameters of a power system. The method is based on explicitly expressing the system state matrix into sub-matrices. The eigenvalue sensitivity is calculated based on the explicitly formed system state matrix. The 4th order generator model and 4th order exciter system model are used to form the system state matrix. A case study using New England 10-machine 39-bus system is provided to demonstrate the effectiveness of the proposed method. This method can be applied into large scale power system eigenvalue sensitivity with respect to operating parameters.

Identificador

http://espace.library.uq.edu.au/view/UQ:104286

Idioma(s)

eng

Publicador

The Institution of Engineering and Technology Hong Kong

Palavras-Chave #E1 #290901 Electrical Engineering #660304 Energy systems analysis
Tipo

Conference Paper