A novel ground fault non-directional selective protection method for ungrounded distribution networks


Autoria(s): Granizo Arrabe, Ricardo; Blánquez Delgado, Francisco; Rebollo López, Emilio; Platero Gaona, Carlos Antonio
Data(s)

2015

Resumo

This paper presents a new selective and non-directional protection method to detect ground faults in neutral isolated power systems. The new proposed method is based on the comparison of the rms value of the residual current of all the lines connected to a bus, and it is able to determine the line with ground defect. Additionally, this method can be used for the protection of secondary substation. This protection method avoids the unwanted trips produced by wrong settings or wiring errors, which sometimes occur in the existing directional ground fault protections. This new method has been validated through computer simulations and experimental laboratory tests.

Formato

application/pdf

Identificador

http://oa.upm.es/40643/

Idioma(s)

eng

Publicador

E.T.S.I. Diseño Industrial (UPM)

Relação

http://oa.upm.es/40643/1/INVE_MEM_2015_191632.pdf

http://www.mdpi.com/1996-1073/8/2/1291

info:eu-repo/semantics/altIdentifier/doi/10.3390/en8021291

Direitos

http://creativecommons.org/licenses/by-nc-nd/3.0/es/

info:eu-repo/semantics/openAccess

Fonte

Energies, ISSN 1996-1073, 2015, Vol. 8, No. 2

Palavras-Chave #Energía Eléctrica #Electrónica
Tipo

info:eu-repo/semantics/article

Artículo

PeerReviewed