Contribution to Load-Frequency Regulation of a Hydropower Plant with Long Tail-Race Tunnel
Data(s) |
2015
31/12/1969
|
---|---|
Resumo |
In this paper, a hydroelectric power plant with long tail-race tunnel has been modelled for assessing its contribution to secondary regulation reserve. Cavitation problems, caused by the discharge conduit length, are expected downstream the turbine where low pressure appears during regulation manoeuvres. Therefore, governor's gains should be selected taking into account these phenomena. On the other hand, regulation services bidden by the plant operator should fulfil TSO (Transmission System Operator) quality requirements. A methodology for tuning governor PI gains is proposed and applied to a Hydro power plant in pre-design phase in northwest area of Spain. The PI gains adjustment proposed provides a proper plant response, according to some established indexes, while avoiding cavitation phenomena. |
Formato |
application/pdf |
Identificador | |
Idioma(s) |
eng |
Publicador |
E.T.S.I. Caminos, Canales y Puertos (UPM) |
Relação |
http://oa.upm.es/37618/1/INVE_MEM_2015_199102.pdf http://www.ieee.org/conferences_events/conferences/conferencedetails/index.html?Conf_ID=35013 ENE2012-32207 info:eu-repo/semantics/altIdentifier/doi/10.1109/EEEIC.2015.7165460 |
Direitos |
http://creativecommons.org/licenses/by-nc-nd/3.0/es/ info:eu-repo/semantics/embargoedAccess |
Fonte |
Environment and Electrical Engineering (EEEIC), 2015 IEEE 15th International Conference on | 2015 IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC) | 10/06/2015-13/06/2015 | Rome, Italy |
Palavras-Chave | #Energía Eléctrica #Ingeniería Civil y de la Construcción |
Tipo |
info:eu-repo/semantics/conferenceObject Ponencia en Congreso o Jornada PeerReviewed |