New On-Line Excitation-System Ground Fault Location Method Tested in a 106 MVA Synchronous Generator


Autoria(s): Blánquez Delgado, Francisco; Pardo, Miguel; Platero Gaona, Carlos Antonio; Rebollo López, Emilio; Blázquez García, Francisco
Data(s)

2014

Resumo

In this paper, a novel excitation-system ground-fault location method is described and tested in a 106 MVA synchronous machine. In this unit, numerous rotor ground-fault trips took place always about an hour after the synchronization to the network. However, when the field winding insulation was checked after the trips, there was no failure. The data indicated that the faults in the rotor were caused by centrifugal forces and temperature. Unexpectedly, by applying this new method, the failure was located in a cable between the excitation transformer and the automatic voltage regulator. In addition, several intentional ground faults were performed along the field winding with different fault resistance values, in order to test the accuracy of this method to locate defects in rotor windings of large generators. Therefore, this new on-line rotor ground-fault detection algorithm is tested in high-power synchronous generators with satisfactory results.

Formato

application/pdf

Identificador

http://oa.upm.es/36306/

Idioma(s)

eng

Publicador

E.T.S.I. Industriales (UPM)

Relação

http://oa.upm.es/36306/1/INVE_MEM_2014_188126.pdf

http://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=6945619

Direitos

http://creativecommons.org/licenses/by-nc-nd/3.0/es/

info:eu-repo/semantics/openAccess

Fonte

Proceedings 2014 International Conference on Electrical Machines (ICEM) | 2014 International Conference on Electrical Machines (ICEM) | 02 - 05 September 2014 | Berlin, Germany

Palavras-Chave #Energía Eléctrica
Tipo

info:eu-repo/semantics/conferenceObject

Ponencia en Congreso o Jornada

NonPeerReviewed