Consideration of Multi-Phase Criterion in the Differential Protection Algorithm for High-Impedance Grounded Synchronous Generators


Autoria(s): Blánquez Delgado, Francisco; Rebollo López, Emilio; Granizo Arrabe, Ricardo; Platero Gaona, Carlos Antonio
Data(s)

2013

Resumo

The generator differential protection is one of the most important electrical protections of synchronous generator stator windings. Its operation principle is based on the comparison of the input current and output current at each phase winding. Unwanted trip commands are usually caused by CT saturation, wrong CT selection, or the fact that they may come from different manufacturers. In generators grounded through high impedance, only phase-to-phase or three-phase faults can be detected by the differential protection. This kind of fault causes differential current to flow in, at least, two phases of the winding. Several cases of unwanted trip commands caused by the appearance of differential current in only one phase of the generator have been reported. In this paper multi-phase criterion is proposed for generator differential protection algorithm when applied to high impedance grounded generators.

Formato

application/pdf

Identificador

http://oa.upm.es/29670/

Idioma(s)

eng

Publicador

E.T.S.I. Industriales (UPM)

Relação

http://oa.upm.es/29670/1/INVE_MEM_2013_169838.pdf

http://ieeexplore.ieee.org/xpls/abs_all.jsp?arnumber=6549604&tag=1

info:eu-repo/semantics/altIdentifier/doi/null

Direitos

http://creativecommons.org/licenses/by-nc-nd/3.0/es/

info:eu-repo/semantics/openAccess

Fonte

12th International Conference on Environment and Electrical Engineering. EEEIC 2013 | 12th International Conference on Environment and Electrical Engineering. EEEIC 2013 | 05/05/2013 - 08/05/2013 | Wroclaw, Poland

Palavras-Chave #Energía Eléctrica
Tipo

info:eu-repo/semantics/conferenceObject

Ponencia en Congreso o Jornada

PeerReviewed