Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System.
Data(s) |
15/06/2016
|
---|---|
Resumo |
Heater-cooler units (HCUs) were recently identified as a source of Mycobacterium chimaera causing surgical site infections. We investigated transmission of this bacterium from HCUs to the surgical field by using a thermic anemometer and particle counter, videotape of an operating room equipped with an ultraclean laminar airflow ventilation system, and bacterial culture sedimentation plates in a nonventilated room. Smoke from the HCU reached the surgical field in 23 s by merging with ultraclean air. The HCU produced on average 5.2, 139, and 14.8 particles/min in the surgical field at positions Off, On/oriented toward, and On/oriented away, respectively. Culture plates were positive for M. chimaera <5 m from the HCU in the test room. These experiments confirm airborne transmission of M. chimaera aerosols from a contaminated HCU to an open surgical field despite ultraclean air ventilation. Efforts to mitigate infectious risks during surgery should consider contamination from water sources and airflow-generating devices. |
Formato |
application/pdf |
Identificador |
http://boris.unibe.ch/81234/2/16-0045.pdf Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P; Sax, Hugo (2016). Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System. Emerging infectious diseases, 22(6), pp. 1008-1013. U.S. National Center for Infectious Diseases 10.3201/eid2206.160045 <http://dx.doi.org/10.3201/eid2206.160045> doi:10.7892/boris.81234 info:doi:10.3201/eid2206.160045 info:pmid:27070958 urn:issn:1080-6040 |
Idioma(s) |
eng |
Publicador |
U.S. National Center for Infectious Diseases |
Relação |
http://boris.unibe.ch/81234/ |
Direitos |
info:eu-repo/semantics/openAccess |
Fonte |
Sommerstein, Rami; Rüegg, Christian; Kohler, Philipp; Bloemberg, Guido; Kuster, Stefan P; Sax, Hugo (2016). Transmission of Mycobacterium chimaera from Heater-Cooler Units during Cardiac Surgery despite an Ultraclean Air Ventilation System. Emerging infectious diseases, 22(6), pp. 1008-1013. U.S. National Center for Infectious Diseases 10.3201/eid2206.160045 <http://dx.doi.org/10.3201/eid2206.160045> |
Palavras-Chave | #610 Medicine & health |
Tipo |
info:eu-repo/semantics/article info:eu-repo/semantics/publishedVersion PeerReviewed |