An approach of optimal sensitivity applied in the tertiary loop of the automatic generation control


Autoria(s): Belati, Edmarcio A.; Alves, Dilson A.; da Costa, Geraldo R. M.
Contribuinte(s)

Universidade Estadual Paulista (UNESP)

Data(s)

20/05/2014

20/05/2014

01/09/2008

Resumo

This paper proposes an approach of optimal sensitivity applied in the tertiary loop of the automatic generation control. The approach is based on the theorem of non-linear perturbation. From an optimal operation point obtained by an optimal power flow a new optimal operation point is directly determined after a perturbation, i.e., without the necessity of an iterative process. This new optimal operation point satisfies the constraints of the problem for small perturbation in the loads. The participation factors and the voltage set point of the automatic voltage regulators (AVR) of the generators are determined by the technique of optimal sensitivity, considering the effects of the active power losses minimization and the network constraints. The participation factors and voltage set point of the generators are supplied directly to a computational program of dynamic simulation of the automatic generation control, named by power sensitivity mode. Test results are presented to show the good performance of this approach. (C) 2008 Elsevier B.V. All rights reserved.

Formato

1553-1560

Identificador

http://dx.doi.org/10.1016/j.epsr.2008.01.017

Electric Power Systems Research. Lausanne: Elsevier B.V. Sa, v. 78, n. 9, p. 1553-1560, 2008.

0378-7796

http://hdl.handle.net/11449/40064

10.1016/j.epsr.2008.01.017

WOS:000257619800009

Idioma(s)

eng

Publicador

Elsevier B.V. Sa

Relação

Electric Power Systems Research

Direitos

closedAccess

Palavras-Chave #automatic generation control #load frequency control #area control error #optimal power flow #active power loss minimization
Tipo

info:eu-repo/semantics/article