Improved Fault Location on Distribution Feeders Based on Matching During-Fault Voltage Sags


Autoria(s): Fernandes Pereira, Rodrigo Aparecido; Wesz da Silva, Luis Gustavo; Kezunovic, Mladen; Sanches Mantovani, Jose Roberto
Contribuinte(s)

Universidade Estadual Paulista (UNESP)

Data(s)

20/05/2014

20/05/2014

01/04/2009

Resumo

Coordenação de Aperfeiçoamento de Pessoal de Nível Superior (CAPES)

Conselho Nacional de Desenvolvimento Científico e Tecnológico (CNPq)

A fault location algorithm for distribution feeders based on matching during-fault voltage sags is presented. The basic principle of the algorithm is based on the fact that when a fault occurs on the feeder, voltage sags propagate presenting different characteristics for each feeder node. Knowing the voltage sag characteristics, it is possible to locate the faulty node or the faulty area of the feeder. This voltage-based approach ensures the efficiency and robustness of the algorithm, which provides suitable and accurate results. An overhead, three-phase, three-wire, 13.8 kV, 134-node, real-life feeder model is used to evaluate the algorithm. Test results show that the algorithm is quite suitable due to not only the faulted point being located, but also a faulted area being identified providing important information to direct the maintenance crew seeking to repair any fault inflicted damage.

Formato

852-862

Identificador

http://dx.doi.org/10.1109/TPWRD.2009.2014480

IEEE Transactions on Power Delivery. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 24, n. 2, p. 852-862, 2009.

0885-8977

http://hdl.handle.net/11449/9857

10.1109/TPWRD.2009.2014480

WOS:000265093000044

Idioma(s)

eng

Publicador

Institute of Electrical and Electronics Engineers (IEEE)

Relação

IEEE Transactions on Power Delivery

Direitos

closedAccess

Palavras-Chave #Fault location #power distribution #voltage measurement #voltage sags
Tipo