Improved Fault Location on Distribution Feeders Based on Matching During-Fault Voltage Sags
Contribuinte(s) |
Universidade Estadual Paulista (UNESP) |
---|---|
Data(s) |
20/05/2014
20/05/2014
01/04/2009
|
Resumo |
Coordenação de Aperfeiçoamento de Pessoal de Nível Superior (CAPES) Conselho Nacional de Desenvolvimento Científico e Tecnológico (CNPq) A fault location algorithm for distribution feeders based on matching during-fault voltage sags is presented. The basic principle of the algorithm is based on the fact that when a fault occurs on the feeder, voltage sags propagate presenting different characteristics for each feeder node. Knowing the voltage sag characteristics, it is possible to locate the faulty node or the faulty area of the feeder. This voltage-based approach ensures the efficiency and robustness of the algorithm, which provides suitable and accurate results. An overhead, three-phase, three-wire, 13.8 kV, 134-node, real-life feeder model is used to evaluate the algorithm. Test results show that the algorithm is quite suitable due to not only the faulted point being located, but also a faulted area being identified providing important information to direct the maintenance crew seeking to repair any fault inflicted damage. |
Formato |
852-862 |
Identificador |
http://dx.doi.org/10.1109/TPWRD.2009.2014480 IEEE Transactions on Power Delivery. Piscataway: IEEE-Inst Electrical Electronics Engineers Inc, v. 24, n. 2, p. 852-862, 2009. 0885-8977 http://hdl.handle.net/11449/9857 10.1109/TPWRD.2009.2014480 WOS:000265093000044 |
Idioma(s) |
eng |
Publicador |
Institute of Electrical and Electronics Engineers (IEEE) |
Relação |
IEEE Transactions on Power Delivery |
Direitos |
closedAccess |
Palavras-Chave | #Fault location #power distribution #voltage measurement #voltage sags |
Tipo |
info:eu-repo/semantics/article |