Parameterized fast decoupled power flow methods for obtaining the maximum loading point of power systems. Part I. Mathematical modeling


Autoria(s): Alves, D. A.; da Silva, LCP; Castro, C. A.; da Costa, V. F.
Contribuinte(s)

Universidade Estadual Paulista (UNESP)

Data(s)

20/05/2014

20/05/2014

01/04/2004

Resumo

The conventional Newton and fast decoupled power flow (FDPF) methods have been considered inadequate to obtain the maximum loading point of power systems due to ill-conditioning problems at and near this critical point. It is well known that the PV and Q-theta decoupling assumptions of the fast decoupled power flow formulation no longer hold in the vicinity of the critical point. Moreover, the Jacobian matrix of the Newton method becomes singular at this point. However, the maximum loading point can be efficiently computed through parameterization techniques of continuation methods. In this paper it is shown that by using either theta or V as a parameter, the new fast decoupled power flow versions (XB and BX) become adequate for the computation of the maximum loading point only with a few small modifications. The possible use of reactive power injection in a selected PV bus (Q(PV)) as continuation parameter (mu) for the computation of the maximum loading point is also shown. A trivial secant predictor, the modified zero-order polynomial which uses the current solution and a fixed increment in the parameter (V, theta, or mu) as an estimate for the next solution, is used in predictor step. These new versions are compared to each other with the purpose of pointing out their features, as well as the influence of reactive power and transformer tap limits. The results obtained with the new approach for the IEEE test systems (14, 30, 57 and 118 buses) are presented and discussed in the companion paper. The results show that the characteristics of the conventional method are enhanced and the region of convergence around the singular solution is enlarged. In addition, it is shown that parameters can be switched during the tracing process in order to efficiently determine all the PV curve points with few iterations. (C) 2003 Elsevier B.V. All rights reserved.

Formato

93-104

Identificador

http://dx.doi.org/10.1016/j.epsr.2003.08.009

Electric Power Systems Research. Lausanne: Elsevier B.V. Sa, v. 69, n. 1, p. 93-104, 2004.

0378-7796

http://hdl.handle.net/11449/9665

10.1016/j.epsr.2003.08.009

WOS:000187963200012

Idioma(s)

eng

Publicador

Elsevier B.V.

Relação

Electric Power Systems Research

Direitos

closedAccess

Palavras-Chave #continuation power flow #fast decoupled power flow #maximum loading point #voltage collapse
Tipo

info:eu-repo/semantics/article