Impact of high PV penetration into distribution networks under contingencies
Contribuinte(s) |
[Unknown] |
---|---|
Data(s) |
01/01/2013
|
Resumo |
This paper analyzes the static voltage stability of distribution networks with photovoltaic (PV) generators under contingencies. The analysis is carried out on a widely used 16-bus test system. The paper treats the Q-V characteristics of the distribution grid for various PV penetration levels. Simulation results show that a higher penetration of PV increases the static coltage stability of the system. However, the tripping of multiple PV generators due to external disturbances, overloading and loss of distribution lines reduces the voltage stability margin of the system. |
Identificador | |
Idioma(s) |
eng |
Publicador |
IEEE |
Relação |
http://dro.deakin.edu.au/eserv/DU:30064221/roy-impacthighpv-2013.pdf http://doi.org/10.1109/SEGE.2013.6707919 |
Direitos |
2013, IEEE |
Palavras-Chave | #distributed generation #photovoltaic generator #Q-V characteristics #voltage stability |
Tipo |
Conference Paper |