Monitoring results of combined pellet and solar heating system


Autoria(s): Fiedler, Frank; Bales, Chris; Vestlund, Johan
Data(s)

2007

Resumo

In this study the monitoring results of prototype installation of a recently developed solar combisystem have been evaluated. The system, that uses a water jacketed pellet stove as auxiliary heater, was installed in a single family house in Borlänge/Sweden. In order to allow an evaluation under realistic conditions the system has been monitored for a time period of one year. From the measurements of the system it could be seen that it is important that the pellet stove has a sufficient buffer store volume to minimize cycling. The measurements showed also that the stove gives a lower share of the produced heat to the water loop than measured under stationary conditions. The solar system works as expected and covers the heat demand during the summer and a part of the heat demand during spring and autumn. Potential for optimization exists for the parasitic electricity demand. The system consumes 680 kWh per year for pumps, valves and controllers which is more than 4% of the total primary heating energy demand.

Formato

application/pdf

Identificador

http://urn.kb.se/resolve?urn=urn:nbn:se:du-2922

Idioma(s)

eng

Publicador

Högskolan Dalarna, Energi och miljöteknik

Högskolan Dalarna, Energi och miljöteknik

Högskolan Dalarna, Energi och miljöteknik

Relação

ISES Solar World Congress 2007, ISES 2007, p. 867-871

Direitos

info:eu-repo/semantics/openAccess

Palavras-Chave #Solar and pellet heating systems
Tipo

Conference paper

info:eu-repo/semantics/conferenceObject

text