“Qualitative Air Flow Modelling And Analysis Of Data Centre Air Conditioning As Multiple Jet Array
Data(s) |
25/04/2014
25/04/2014
01/11/2011
|
---|---|
Resumo |
In the present study the effect of hot air recirculation is studied with suitable assumptions. It identifies that, the pressure drop across the tile is a dominant parameter which governs the recirculation. The rack suction pressure of the hardware along with the pressure drop across the tile determines the point of recirculation in the cold aisle. The positioning of hardware in the racks play an important role in controlling the recirculation point. The present study is thus helpful in the design of data centre air flow, based on the theory of jets. The air flow can be modelled both quantitatively and qualitatively based on the results Division Of Safety And Fire Engineering School Of Engineering Cochin University Of Science And Technology Cochin University Of Science And Technology |
Identificador | |
Idioma(s) |
en |
Publicador |
Cochin University Of Science And Technology |
Palavras-Chave | #Data Centre air Conditioning #Single Jet #Twin Jet #Triple Jet #Tile Calculations |
Tipo |
Thesis |