Qualitative air flow modelling and analysis of data centre air conditioning as multiple jet array


Autoria(s): Premnath, R; Dr.Madhu, G
Data(s)

26/02/2014

26/02/2014

01/11/2011

Resumo

This work identifies the importance of plenum pressure on the performance of the data centre. The present methodology followed in the industry considers the pressure drop across the tile as a dependant variable, but it is shown in this work that this is the only one independent variable that is responsible for the entire flow dynamics in the data centre, and any design or assessment procedure must consider the pressure difference across the tile as the primary independent variable. This concept is further explained by the studies on the effect of dampers on the flow characteristics. The dampers have found to introduce an additional pressure drop there by reducing the effective pressure drop across the tile. The effect of damper is to change the flow both in quantitative and qualitative aspects. But the effect of damper on the flow in the quantitative aspect is only considered while using the damper as an aid for capacity control. Results from the present study suggest that the use of dampers must be avoided in data centre and well designed tiles which give required flow rates must be used in the appropriate locations. In the present study the effect of hot air recirculation is studied with suitable assumptions. It identifies that, the pressure drop across the tile is a dominant parameter which governs the recirculation. The rack suction pressure of the hardware along with the pressure drop across the tile determines the point of recirculation in the cold aisle. The positioning of hardware in the racks play an important role in controlling the recirculation point. The present study is thus helpful in the design of data centre air flow, based on the theory of jets. The air flow can be modelled both quantitatively and qualitatively based on the results.

Division of Safety and Fire Engineering, School of Engineering, Cochin University of Science and Technology

Cochin University of Science and Technology

Identificador

http://dyuthi.cusat.ac.in/purl/3264

Idioma(s)

en

Publicador

Cochin University of Science and Technology

Palavras-Chave #Data Centre air Conditioning #Single Jet #Twin Jet #Triple Jet #Tile Calculations #Effect of Damper
Tipo

Thesis