Performance Improvement of Centrifugal Compressor Stage with Pinched Geometry or Vaned Diffuser


Autoria(s): Jaatinen, Ahti
Data(s)

15/09/2009

15/09/2009

01/10/2009

Resumo

Centrifugal compressors are widely used for example in refrigeration processes, the oil and gas industry, superchargers, and waste water treatment. In this work, five different vaneless diffusers and six different vaned diffusers are investigated numerically. The vaneless diffusers vary only by their diffuser width, so that four of the geometries have pinch implemented to them. Pinch means a decrease in the diffuser width. Four of the vaned diffusers have the same vane turning angle and a different number of vanes, and two have different vane turning angles. The flow solver used to solve the flow fields is Finflo, which is a Navier-Stokes solver. All the cases are modeled with the Chien's k – έ- turbulence model, and selected cases are modeled also with the k – ώ-SST turbulence model. All five vaneless diffusers and three vaned diffusers are investigated also experimentally. For each construction, the compressor operating map is measured according to relevant standards. In addition to this, the flow fields before and after the diffuser are measured with static and total pressure, flow angle and total temperature measurements. When comparing the computational results to the measured results, it is evident that the k – ώ-SST turbulence model predicts the flow fields better. The simulation results indicate that it is possible to improve the efficiency with the pinch, and according to the numerical results, the two best geometries are the ones with most pinch at the shroud. These geometries have approximately 4 percentage points higher efficiency than the unpinched vaneless diffusers. The hub pinch does not seem to have any major benefits. In general, the pinches make the flow fields before and after the diffuser more uniform. The pinch also seems to improve the impeller efficiency. This is down to two reasons. The major reason is that the pinch decreases the size of slow flow and possible backflow region located near the shroud after the impeller. Secondly, the pinches decrease the flow velocity in the tip clearance, leading to a smaller tip leakage flow and therefore slightly better impeller efficiency. Also some of the vaned diffusers improve the efficiency, the increment being 1...3 percentage points, when compared to the vaneless unpinched geometry. The measurement results confirm that the pinch is beneficial to the performance of the compressor. The flow fields are more uniform with the pinched cases, and the slow flow regions are smaller. The peak efficiency is approximately 2 percentage points and the design point efficiency approximately 4 percentage points higher with the pinched geometries than with the un- pinched geometry. According to the measurements, the two best geometries are the ones with the most pinch at the shroud, the case with the pinch only at the shroud being slightly better of the two. The vaned diffusers also have better efficiency than the vaneless unpinched geometries. However, the pinched cases have even better efficiencies. The vaned diffusers narrow the operating range considerably, whilst the pinch has no significant effect on the operating range.

Identificador

978-952-214-821-6

1456-4491

http://www.doria.fi/handle/10024/47003

URN:ISBN:978-952-214-821-6

Idioma(s)

en

Publicador

Lappeenranta University of Technology

Relação

978-952-214-820-9

Acta Universitatis Lappeenrantaensis

Palavras-Chave #centrifugal compressor #diffuser #diffuser width #pinch #vaned diffuser #computational fluid dynamics
Tipo

Väitöskirja

Doctoral Dissertation