Closed-loop model re-identification of processes under MPC with zone control
Contribuinte(s) |
UNIVERSIDADE DE SÃO PAULO |
---|---|
Data(s) |
18/10/2012
18/10/2012
2009
|
Resumo |
This work deals with a procedure for model re-identification of a process in closed loop with ail already existing commercial MPC. The controller considered here has a two-layer structure where the upper layer performs a target calculation based on a simplified steady-state optimization of the process. Here, it is proposed a methodology where a test signal is introduced in a tuning parameter of the target calculation layer. When the outputs are controlled by zones instead of at fixed set points, the approach allows the continuous operation of the process without an excessive disruption of the operating objectives as process constraints and product specifications remain satisfied during the identification test. The application of the method is illustrated through the simulation of two processes of the oil refining industry. (c) 2008 Elsevier Ltd. All rights reserved. Fundacao Universidade de Sao Paulo (FUSP) PETROBRAS[0050.0014884.05.2] |
Identificador |
CONTROL ENGINEERING PRACTICE, v.17, n.5, p.551-563, 2009 0967-0661 http://producao.usp.br/handle/BDPI/18835 10.1016/j.conengprac.2008.10.002 |
Idioma(s) |
eng |
Publicador |
PERGAMON-ELSEVIER SCIENCE LTD |
Relação |
Control Engineering Practice |
Direitos |
restrictedAccess Copyright PERGAMON-ELSEVIER SCIENCE LTD |
Palavras-Chave | #Closed-loop identification #Model predictive control #Model retrofitting #PREDICTIVE CONTROL #CONTROL-SYSTEMS #IDENTIFICATION #IDENTIFIABILITY #PERFORMANCE #Automation & Control Systems #Engineering, Electrical & Electronic |
Tipo |
article original article publishedVersion |