Redundancy and Observability Analysis of Conventional and PMU Measurements


Autoria(s): LONDON JR., J. B. A.; Piereti, Saulo Augusto Ribeiro; BENEDITO, R. A. S.; BRETAS, N. G.
Contribuinte(s)

UNIVERSIDADE DE SÃO PAULO

Data(s)

18/10/2012

18/10/2012

2009

Resumo

This letter shows that the matrix can be used for redundancy and observability analysis of metering systems composed of PMU measurements and conventional measurements (power and voltage magnitude measurements). The matrix is obtained via triangular factorization of the Jacobian matrix. Observability analysis and restoration is carried out during the triangular factorization of the Jacobian matrix, and the redundancy analysis is made exploring the matrix structure. As a consequence, the matrix can be used for metering system planning considering conventional and PMU measurements. These features of the matrix will be outlined and illustrated by numerical examples.

Identificador

IEEE TRANSACTIONS ON POWER SYSTEMS, v.24, n.3, p.1629-1630, 2009

0885-8950

http://producao.usp.br/handle/BDPI/17738

10.1109/TPWRS.2009.2021195

http://dx.doi.org/10.1109/TPWRS.2009.2021195

Idioma(s)

eng

Publicador

IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

Relação

Ieee Transactions on Power Systems

Direitos

restrictedAccess

Copyright IEEE-INST ELECTRICAL ELECTRONICS ENGINEERS INC

Palavras-Chave #Network observability #phasor measurement units #redundancy analysis #state estimation #STATE-ESTIMATION #Engineering, Electrical & Electronic
Tipo

article

original article

publishedVersion