Combined solution for fault location in three-terminal lines based on wavelet transforms


Autoria(s): SILVA, M. da; COURY, D. V.; OLESKOVICZ, M.; SEGATTO, E. C.
Contribuinte(s)

UNIVERSIDADE DE SÃO PAULO

Data(s)

18/10/2012

18/10/2012

2010

Resumo

This work presents the study and development of a combined fault location scheme for three-terminal transmission lines using wavelet transforms (WTs). The methodology is based on the low- and high-frequency components of the transient signals originated from fault situations registered in the terminals of a system. By processing these signals and using the WT, it is possible to determine the time of travelling waves of voltages and/or currents from the fault point to the terminals, as well as estimate the fundamental frequency components. A new approach presents a reliable and accurate fault location scheme combining some different solutions. The main idea is to have a decision routine in order to select which method should be used in each situation presented to the algorithm. The combined algorithm was tested for different fault conditions by simulations using the ATP (Alternative Transients Program) software. The results obtained are promising and demonstrate a highly satisfactory degree of accuracy and reliability of the proposed method.

CAPES Coordenacao de Aperfeicoamento de Pessoal de Nivel Superior

Identificador

IET GENERATION TRANSMISSION & DISTRIBUTION, v.4, n.1, p.94-103, 2010

1751-8687

http://producao.usp.br/handle/BDPI/17730

10.1049/iet-gtd.2009.0249

http://dx.doi.org/10.1049/iet-gtd.2009.0249

Idioma(s)

eng

Publicador

INST ENGINEERING TECHNOLOGY-IET

Relação

Iet Generation Transmission & Distribution

Direitos

restrictedAccess

Copyright INST ENGINEERING TECHNOLOGY-IET

Palavras-Chave #TRANSMISSION-LINES #ALGORITHM #Engineering, Electrical & Electronic
Tipo

article

original article

publishedVersion