Power imbalance application region method for distributed synchronous generator anti-islanding protection design and evaluation


Autoria(s): VIEIRA, Jose C. M.; SALLES, Diogo; FREITAS, Walmir
Contribuinte(s)

UNIVERSIDADE DE SÃO PAULO

Data(s)

18/10/2012

18/10/2012

2011

Resumo

This paper presents a novel graphical approach to adjust and evaluate frequency-based relays employed in anti-islanding protection schemes of distributed synchronous generators, in order to meet the anti-islanding and abnormal frequency variation requirements, simultaneously. The proposed method defines a region in the power mismatch space, inside which the relay non-detection zone should be located, if the above-mentioned requirements must be met. Such region is called power imbalance application region. Results show that this method can help protection engineers to adjust frequency-based relays to improve the anti-islanding capability and to minimize false operation occurrences, keeping the abnormal frequency variation utility requirements satisfied. Moreover, the proposed method can be employed to coordinate different types of frequency-based relays, aiming at improving overall performance of the distributed generator frequency protection scheme. (C) 2011 Elsevier B.V. All rights reserved.

Brazilian government via FAPESP (State of Sao Paulo Research Foundation)

Identificador

ELECTRIC POWER SYSTEMS RESEARCH, v.81, n.10, p.1952-1960, 2011

0378-7796

http://producao.usp.br/handle/BDPI/17729

10.1016/j.epsr.2011.06.009

http://dx.doi.org/10.1016/j.epsr.2011.06.009

Idioma(s)

eng

Publicador

ELSEVIER SCIENCE SA

Relação

Electric Power Systems Research

Direitos

restrictedAccess

Copyright ELSEVIER SCIENCE SA

Palavras-Chave #Distributed generation #Frequency protection #Islanding #Non-detection zone #Synchronous generator #DISPERSED STORAGE #VOLTAGE #Engineering, Electrical & Electronic
Tipo

article

original article

publishedVersion