Digital frequency relaying based on the modified least mean square method


Autoria(s): BARBOSA, Daniel; MONARO, Renato M.; COURY, Denis V.; OLESKOVICZ, Mario
Contribuinte(s)

UNIVERSIDADE DE SÃO PAULO

Data(s)

18/10/2012

18/10/2012

2010

Resumo

This research presents a method for frequency estimation in power systems using an adaptive filter based on the Least Mean Square Algorithm (LMS). In order to analyze a power system, three-phase voltages were converted into a complex signal applying the alpha beta-transform and the results were used in an adaptive filtering algorithm. Although the use of the complex LMS algorithm is described in the literature, this paper deals with some practical aspects of the algorithm implementation. In order to reduce computing time, a coefficient generator was implemented. For the algorithm validation, a computing simulation of a power system was carried Out using the ATP software. Many different situations were Simulated for the performance analysis of the proposed methodology. The results were compared to a commercial relay for validation, showing the advantages of the new method. (C) 2009 Elsevier Ltd. All rights reserved.

CAPES (Coordenacao de Aperfeicoamento de Pessoal de Nivel Superior)

CNPQ (Conselho Nacional de Desenvolvimento Cientifico e Tecnologico)

FAPESP (Fundacao de Amparo a Pesquisa do Estado de Sao Paulo)

Identificador

INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, v.32, n.3, p.236-242, 2010

0142-0615

http://producao.usp.br/handle/BDPI/17727

10.1016/j.ijepes.2009.07.009

http://dx.doi.org/10.1016/j.ijepes.2009.07.009

Idioma(s)

eng

Publicador

ELSEVIER SCI LTD

Relação

International Journal of Electrical Power & Energy Systems

Direitos

restrictedAccess

Copyright ELSEVIER SCI LTD

Palavras-Chave #Frequency estimation #Adaptive filter #Digital protection #Power system #Least mean square #POWER-SYSTEM FREQUENCY #LMS ALGORITHM #TRACKING #SIGNALS #Engineering, Electrical & Electronic
Tipo

article

original article

publishedVersion