Droop setting design for multi-terminal HVDC grids considering voltage deviation impacts


Autoria(s): Zhao, Xiaodong; Li, Kang
Data(s)

01/06/2015

Resumo

<p>In multi-terminal high voltage direct current (HVDC) grids, the widely deployed droop control strategies will cause a non-uniform voltage deviation on the power flow, which is determined by the network topology and droop settings. This voltage deviation results in an inconsistent power flow pattern when the dispatch references are changed, which could be detrimental to the operation and seamless integration of HVDC grids. In this paper, a novel droop setting design method is proposed to address this problem for a more precise power dispatch. The effects of voltage deviations on the power sharing accuracy and transmission loss are analysed. This paper shows that there is a trade-off between minimizing the voltage deviation, ensuring a proper power delivery and reducing the total transmission loss in the droop setting design. The efficacy of the proposed method is confirmed by simulation studies.</p>

Identificador

http://pure.qub.ac.uk/portal/en/publications/droop-setting-design-for-multiterminal-hvdc-grids-considering-voltage-deviation-impacts(1533de02-e72d-4e0b-b3fa-e82b57a712a8).html

http://dx.doi.org/10.1016/j.epsr.2015.01.022

Idioma(s)

eng

Direitos

info:eu-repo/semantics/restrictedAccess

Fonte

Zhao , X & Li , K 2015 , ' Droop setting design for multi-terminal HVDC grids considering voltage deviation impacts ' Electric Power Systems Research , vol 123 , pp. 67-75 . DOI: 10.1016/j.epsr.2015.01.022

Palavras-Chave #DC grid #Droop control #HVDC #Multi-terminal #Transmission loss #Voltage source converter (VSC) #/dk/atira/pure/subjectarea/asjc/2100/2102 #Energy Engineering and Power Technology #/dk/atira/pure/subjectarea/asjc/2200/2208 #Electrical and Electronic Engineering
Tipo

article