Analysis of VSC-based HVDC System under DC Faults


Autoria(s): Rafferty, J.; Morrow, D. J.; Xu, L.
Data(s)

2013

Resumo

This paper analyzes the behavior of a Voltage Source Converter Based HVDC system under DC cable fault conditions. The behavior of the HVDC system during a permanent line-to-earth fault is analyzed, outlining the systems configuration and behavior at each stage of the fault timeline. Operation of the proposed system under a single earthing configurations i.e. Converter (solid) earthed/AC transformer unearthed, was analyzed and simulated, with particular attention paid to the converters operation. It was observed that the development of potential earth loops within the system as a result of DC line- toearth faults leads to substantial overcurrent and results in system configuration oscillation.

Identificador

http://pure.qub.ac.uk/portal/en/publications/analysis-of-vscbased-hvdc-system-under-dc-faults(0b71ef8c-e334-4286-89c9-56643adc7b7c).html

http://dx.doi.org/10.1109/IECON.2013.6699179

Idioma(s)

eng

Publicador

Institute of Electrical and Electronics Engineers (IEEE)

Direitos

info:eu-repo/semantics/restrictedAccess

Fonte

Rafferty , J , Morrow , D J & Xu , L 2013 , Analysis of VSC-based HVDC System under DC Faults . in IECON 2013 - 39th Annual Conference of the IEEE Industrial Electronics Society . IEEE Industrial Electronics Society , Institute of Electrical and Electronics Engineers (IEEE) , NEW YORK , pp. 459-464 , 39th Annual Conference of the IEEE Industrial-Electronics-Society (IECON) , Austria , 10-14 November . DOI: 10.1109/IECON.2013.6699179

Palavras-Chave #DC Fault #HVDC #VSC #Wind Integration
Tipo

contributionToPeriodical