Investigation of heat exchanger inclination in forced-draught air-cooled heat exchangers


Autoria(s): Kennedy, I.J.; Spence, S.W.T.; Spratt, G.R.; Early, J.M.
Data(s)

01/01/2013

Resumo

The purpose of this study is to determine the influence of inclining the heat exchanger relative to the fan in a forced draught air-cooled heat exchanger. Since inclination increases plenum depth, the effect of inclination is also compared with increasing plenum depth without inclination. The experimental study shows that inclination improves thermal performance by only 0.5%, when compared with a baseline non-inclined case with a shallow plenum. Similarly, increasing plenum depth without inclination has a thermal performance benefit of approximately 1%. The numerical study shows that, as the heat exchanger is inclined, the low velocity core at the centre of the heat exchanger moves to one side. © 2013 Elsevier Ltd. All rights reserved.

Formato

application/pdf

Identificador

http://pure.qub.ac.uk/portal/en/publications/investigation-of-heat-exchanger-inclination-in-forceddraught-aircooled-heat-exchangers(f7f9fd6c-7be7-435b-bb37-f632c72c8e1a).html

http://dx.doi.org/10.1016/j.applthermaleng.2013.02.013

http://pure.qub.ac.uk/ws/files/3279284/Investigation_of_heat_exchanger_inclination_in_forced_draught_air_cooled_heat_exchangers.pdf

Idioma(s)

eng

Direitos

info:eu-repo/semantics/openAccess

Fonte

Kennedy , I J , Spence , S W T , Spratt , G R & Early , J M 2013 , ' Investigation of heat exchanger inclination in forced-draught air-cooled heat exchangers ' Applied Thermal Engineering , vol 54 , no. 2 , pp. 413-421 . DOI: 10.1016/j.applthermaleng.2013.02.013

Tipo

article