The use of fault detection and diagnostics to reduce air handling unit energy consumption


Autoria(s): Bruton, Ken
Contribuinte(s)

O'Sullivan, Dominic

Data(s)

28/08/2015

2014

2014

Resumo

The contribution of buildings towards total worldwide energy consumption in developed countries is between 20% and 40%. Heating Ventilation and Air Conditioning (HVAC), and more specifically Air Handling Units (AHUs) energy consumption accounts on average for 40% of a typical medical device manufacturing or pharmaceutical facility’s energy consumption. Studies have indicated that 20 – 30% energy savings are achievable by recommissioning HVAC systems, and more specifically AHU operations, to rectify faulty operation. Automated Fault Detection and Diagnosis (AFDD) is a process concerned with potentially partially or fully automating the commissioning process through the detection of faults. An expert system is a knowledge-based system, which employs Artificial Intelligence (AI) methods to replicate the knowledge of a human subject matter expert, in a particular field, such as engineering, medicine, finance and marketing, to name a few. This thesis details the research and development work undertaken in the development and testing of a new AFDD expert system for AHUs which can be installed in minimal set up time on a large cross section of AHU types in a building management system vendor neutral manner. Both simulated and extensive field testing was undertaken against a widely available and industry known expert set of rules known as the Air Handling Unit Performance Assessment Rules (APAR) (and a later more developed version known as APAR_extended) in order to prove its effectiveness. Specifically, in tests against a dataset of 52 simulated faults, this new AFDD expert system identified all 52 derived issues whereas the APAR ruleset identified just 10. In tests using actual field data from 5 operating AHUs in 4 manufacturing facilities, the newly developed AFDD expert system for AHUs was shown to identify four individual fault case categories that the APAR method did not, as well as showing improvements made in the area of fault diagnosis.

Accepted Version

Not peer reviewed

Formato

application/pdf

Identificador

Bruton, K. 2014. The use of fault detection and diagnostics to reduce air handling unit energy consumption. PhD Thesis, University College Cork.

226

http://hdl.handle.net/10468/1949

Idioma(s)

en

en

Publicador

University College Cork

Direitos

© 2014, Ken Bruton.

http://creativecommons.org/licenses/by-nc-nd/3.0/

Palavras-Chave #HVAC #Energy efficiency #Fault detection and diagnostics #Expert systems #Building management systems #Air handling units
Tipo

Doctoral thesis

Doctoral

PHD (Engineering)