Performance analysis of 1200 kV ceramic disc insulator string under normal and faulted conditions


Autoria(s): Reddy, Subba B; Verma, Alok Ranjan; Naik, Satish B
Data(s)

2015

Resumo

In the recent years there has been a considerable increase in demand for the electrical power requirement in our country. Presently the transmission system voltages has increased to 765 kV ac and 800kV dc, keeping in view of the future demand experimentation and simulation studies for 1200 kV ac and 1100kV dc transmission are under progress. In the present study an attempt is made to compute the surface potential, electric field across the string of ceramic disc insulators used for 1200kV ac systems. The studies are carried out under normal, polluted conditions and for the case of insulator string containing faulty discs. A computer code using surface charge simulation method (SCSM) is developed for the present analysis. Also a new technique which enhances the surface potential and electric field strength for the existing ceramic disc insulators is presented.

Formato

application/pdf

Identificador

http://eprints.iisc.ernet.in/52561/1/Cle_Eff_and_Aff_Ene_for_a_Sus_Fut_75_1114_2015.pdf

Reddy, Subba B and Verma, Alok Ranjan and Naik, Satish B (2015) Performance analysis of 1200 kV ceramic disc insulator string under normal and faulted conditions. In: 7th International Conference on Applied Energy (ICAE), MAR 28-31, 2015, Abu Dhabi, U ARAB EMIRATES, pp. 1114-1119.

Publicador

ELSEVIER SCIENCE BV

Relação

http://dx.doi.org/10.1016/j.egypro.2015.07.522

http://eprints.iisc.ernet.in/52561/

Palavras-Chave #Electrical Engineering
Tipo

Conference Proceedings

NonPeerReviewed